ATTENTION!    Compressor operation is possible within the operating limits 
shown in the diagrams. Please note the signicance 
of the shaded areas. Thresholds should not be selected as design 
or continuous operation points.
         - Permissible ambient temperature (-20°C) - (+60°C)
         - Max. permissible discharge end temperature 140 °C
    -Max.permissibleswitchingfrequency8x/h.
         -  A minimum running time of 3 min. steady-state condition 
 (continuous operation) must be achieved.
 For operation with additional cooling:
         - Use only oils that are highly thermally stable.
         - Avoid continuous operation near the limits.
Foroperationwithfrequencyconverter:
         - The potential control range of the compressor is 30-70 Hz.
         - Max. permissible current consumption must not be exceeded. 
     Atmax.rotationspeedtherefore,theapplicationlimitcan 
     be reduced.
         - Use a thermal protection thermostat.
         - Do not operate an additional capacity controller.
    -Oilreturnatlowfrequencymustbeguaranteed.
    -ConsultationwithGEABock.
 For operation with capacity regulator:
       -  The suction gas superheat temperature may need to be  
          reduced or set individuallywhen operating near to the threshold.
When operating in the vacuum range, there is a danger of air
enteringonthesuctionside.Thiscancausechemicalreactions,
a pressure rise in the condenser and an elevated compressed-gas 
temperature. Prevent the ingress of air at all costs!
3.3  Limits of application
3| Areas of application
 Thecompressorsarelledatthefactorywiththefollowingoiltype:
 - for R134a, R404A/R507, R407C  FUCHS Reniso Triton SE 55 
   - for R22  FUCHS Reniso SP 46 
Compressorswithesteroilcharge(FUCHSRenisoTritonSE55)aremarkedwithanXinthetype
designation (e.g. HGX22e/190-4A).
 3.1  Refrigerants
• HFKW/HFC:  R134a, R404A/R507, R407C
• (H)FCKW/(H)CFC: R22
3.2  Oil  charge
INFO! 
Forrefilling,werecommendtheaboveoiltypes. 
  Alternatives: seelubricantstable,Chapter7.5.
The oil level must be in the 
visible part of the sight 
glass; damage to the com-
pressor is possible if over-
filled or underfilled!
ATTENTION!
max.
min.
0,7 Ltr. 
oil level