Manual
D
GB
F
E
13
96020-02.2015-DGbFEI
5| Electrical connection
5.2 Standardmotor,designfordirectorpartialwindingstart
Designation on the name plate Sticker on the terminal box
Y/YY
Compressors with this marking are suitable for direct or partial winding start. The motor winding is
subdivided into two parts: Partial winding 1 = 66% and part winding 2 = 33%. This winding division
reduces the start-up current needed for a part winding start to approx. 65% of that for a direct start.
400 V
Direktstart YY Teilwicklungsstart Y/YY
1V1 1W11U1
2W12V12U1
L3L2L1 L3L2L1
L3L2L1
1V1 1W11U1
2W12V12U1
Direct start YY
Part winding start Y/YY
The motor is wired for direct start (YY) at the factory. For part winding start (Y/YY) the bridges must be
removed and the motor feed line connected according to the circuit diagram:
INFO A mechanical unloaded start with bypass solenoid valve is
notrequired
ATTENTION Failureto do this results in opposed rotary elds and results in
damage to the motor. After the motor starts up via partial winding
1,partialwinding2mustbeswitchedonafteramaximumdelay
of one second . Failure to comply can adversely affect the service
life of the motor.