6| Commissioning
6.7 Decompression valves
Check that the safety and protection devices (pressure switch, motor protection, electrical contact
protection measures, etc.) are functioning properly.
Switch on the compressor and let it run for at least 10 minutes.
Themachineshouldreachastateofequilibrium.
Check the oil level: The oil level must be visible in the sight glass.
After a compressor is replaced, the oil level must be checked again. If the level is too high, oil
mustbedrainedoff(dangerofoilliquidshocks;reducedcapacityoftherefrigeratingsystem).
CO
2
streaming
out
Fig. 19
WARNING Ensure that both shut-off valves are open before starting the
compressor!
ATTENTION Iflargerquantitiesofoilhavetobetoppedup,thereisariskof
oil hammer effects.
Ifthisisthecasechecktheoilreturn!
ATTENTION Thecompressoristtedwithtwodecompressionvalves.Onevalve
each on the suction and discharge side. If excessive pressures are
reached,thevalvesopenandpreventfurtherpressureincrease.
Thereby CO
2
isblownofftotheambient!(seealsoChapter7.6)!
Intheeventthatapressurereliefvalveactivatesrepeatedly,check
valve and replace if necessary as during blow-off extreme condi-
tions can occure, which may result in a permanent leak.Always
checksystemforrefrigerantlossafteractivationofpressurerelief
valve!
The decompression valves do not replace any pressure switches and the
additional safety valves in the system. Pressure switches must
always be installed in the system and designed or adjusted in
accordance with EN 378-2 or appropriate safety standards.
FailuretoobservecanresultinriskofinjuryfromCO
2
streaming
out of the two decompression valves!