5| Electrical connection 
400 V
Direktstart YY Teilwicklungsstart Y/YY
1V1 1W11U1
2W12V12U1
L3L2L1 L3L2L1
L3L2L1
1V1 1W11U1
2W12V12U1
Direct start YY
 Part winding start Y/YY
ATTENTION! Failure to do this results in opposed rotary elds and results in
damage to the motor. After the motor starts up via partial winding 
1,partialwinding2mustbeswitchedonafteramaximumdelayof
one second . Failure to comply can adversely affect the service life 
of the motor.
The motor is wired for direct start (YY) at the factory. For part winding start Y / YY, the bridges must be 
removed and the motor feed line connected according to the circuit diagram: