User guide
D
GB
F
E
27
96180-01.2015-DGbFEI
8| Technical data
Type
No. of cylinders
Displace-
ment
50/60Hz
(1450 / 1740
rpm)
Electrical data
Weight
Connections
Oil charge
Sound
pressure
level
Voltage Max.
Operating
current
PW 1 + 2
Max.
power
consump
-
tion
Starting
current
(rotorlocked)
PW 1 / PW 1 + 2
Dis-
charge
line
DV
Suction
line
SV
m
3
/h A kW A kg mm (inch) mm (inch) Ltr. dB(A)
HGX5/725-4
R134a
4
62,9 / 75,5 25 14,6 84 / 109 198
28 (1
1
/
8
) 42 (1
5
/
8
)
3,6
70 / 67 / 66
HGX5/830-4
R134a
72,2 / 86,7 28 16,7 84 / 109 197 71 / 68 / 67
HGX5/945-4
R134a
82,2 / 98,6 33 19,1 110 / 141 201 35 (1
3
/
8
) 54 (2
1
/
8
) 72 / 69 / 68
1
2
3
2
4
380-420VY/YY-3-50HzPW
440-480VY/YY-3-60HzPW
PW = Part Winding
Winding ratio: 66% / 33%
L / M / H
5
Tolerance (± 10%) relative to the mean value of the voltage range.
Othervoltagesandtypesofcurrentonrequest.
Take account of the max. operating current / max. power consumption
for design of fuses, supply lines and safety devices. Fuse:
Consumption category AC3
Allspecicationsarebasedontheaverageofthevoltagerange
For solder connections
1
2
3
4
L = low temperature (-35 / 40 °C), M = normal cooling (-10 / 45 °C),
H = air conditioning (5 / 50°C),
sound pressure level measured in
lowreectionmeasuringarea,measuringdistance1m.
Compressor operation at 50 Hz (1450 rpm), refrigerant R404A.
Valuesstatedareaveragevalues,tolerance±2dB(A)
5