Technical Data:
Supply voltage 3 x 400 V AC 50 Hz 15 A
Outputs motor 2 x 3 NO relay contacts,
400 V / 6 A
Wiring 1.5 mm
2
max.,
Operating- -20 ˚C to +60 ˚C
temperature
Caution:
During installation all elements have to be switched tension-free
All installations and service works have to be done by authorized personell only.
The relevant national and local standards and guidelines have to be respected.
Control lamp (optional, only if Comfort module is connected!)
The red LED indicates the most important faults with a flash code:
pre-limit switch defective 1 x flashing
safety edge defective 2 x flashing
limit-switch bottom defective 3 x flashing
safety edge activated 4 x flashing
photo beam defectivet 5 x flashing
resp. light beam interrupted
safety photo beam activated 6 x flashing
safety chain interrupted 7 x flashing
Failure safety photo beam cont. flashing
Function of LED GREEN: LED flashes = door moves DOWN
LED briefly illuminated = door is CLOSED
Connection security limit switches
The security limit switches UP & DOWN have to be connected to the terminals 20/21 &
22/23. If the motor has only 2 wires for the security limit switches then they are connected
to 22/23 & the terminals 20/21 have to be bridged or could be used for another safety
device.
Connection Trademans Entrance/ Lifting wire safety functions
On doors with a built in Wicket Gatethe safety switch is connected with the
terminals 24 & 25.
Connection motor thermoswitch
Connection security limit switch
DOWN
Connection security limit switch
UP
24
25
Connection emergency stop
& wire rope failure
24
25
20
21
22
23
S
S
Connection of primary safety elements
Safety elements which could affect the contactor directly are connected to a separate ter-
minal block. These elements, for example the emergency stop, wire rope failure device
(door catcher), safety device to prevent human entrapment (anti-trapping device) &
Wicket Gateentrance contacts and also the security limit switches (UP & DOWN) are
connected to a separate terminal block.
Connection emergency stop, wire rope failure device & sectional door spring rope
failure device
The safety devices are connected to terminals 26 & 27.
26
27
only
S2