Control Panel Startup/Testing
Installation Guidelines for 60 Hz Air-Cooled Generators 41
2. Verify generator MLCB (generator disconnect) is
OFF (OPEN).
3. Set generator to AUTO mode at the controller.
4. Generator will start and run. Allow generator to run
and warm up for a few minutes.
5. Set MLCB (generator disconnect) to ON
(CLOSED).
6. Set main utility disconnect to ON (CLOSED).
The system now operates in automatic mode.