Owner’s Manual For Automatic Transfer Switch 100 Amp Model Number RTG16EZA3 MODEL NUMBER: _________________________ SERIAL NUMBER: _________________________ DATE PURCHASED:________________________ Register your Generac product at: WWW.GENERAC.COM 888-436-3722 Para español , visita: http://www.generac.com/service‐support/product‐support‐lookup Pour le français, visiter : http://www.generac.
WARNING California Proposition 65. Engine exhaust and some of its constituents are known to the state of California to cause cancer, birth defects, and other reproductive harm. (000004) WARNING California Proposition 65. This product contains or emits chemicals known to the state of California to cause cancer, birth defects, and other reproductive harm.
Table of Contents Table of Contents Section 1 Safety Section 4 Operation 1.1 General ....................................................................1 4.1 Functional Tests and Adjustments ......................9 1.2 General Hazards .....................................................1 4.2 Manual Operation ...................................................9 4.2.1 Close to Utility Source Side ................................9 Section 2 General Information 2.1 Introduction .......................
Table of Contents This page intentionally left blank.
Section 1 Safety 1.1 — General NOTE: Read the following information carefully before attempting to install, operate or service this equipment. Also read the instructions and information on tags, decals, and labels that may be affixed to the transfer switch. Replace any decal or label that is no longer legible. WARNING Consult Manual. Read and understand manual completely before using product. Failure to completely understand manual and product could result in death or serious injury.
Safety • If working on this equipment while standing on metal or concrete, place insulative mats over a dry wood platform. Work on this equipment only while standing on such insulative mats. • Never work on this equipment while physically or mentally fatigued. • Keep the transfer switch enclosure door closed and bolted at all times. Only qualified personnel should be permitted access to the switch interior.
Section 2 General Information 2.1 — Introduction Thank you for purchasing a Generac transfer switch. This manual has been prepared especially for the purpose of familiarizing personnel with the design, application, installation, operation and servicing of the applicable equipment. Read this manual carefully and comply with all instructions. This will help to prevent accidents or damage to equipment that might otherwise be caused by carelessness, incorrect application, or improper procedures.
General Information 2.3.2— Utility Service Circuit Breaker (not supplied) This switch is listed for use with the following one inch breakers: • Siemens* • Murray* • Eaton • Square D *Including GFCI, AFCI and tandem breakers up to 50 amps. NOTE: For branch circuits over 50 amps, only listed Siemens or Murray circuit breakers shall be used. 2.4 — Transfer Switch Data Decal A data decal is permanently affixed to the transfer switch enclosure.
Section 3 Installation 3.1 — Introduction to Installation This equipment has been tested at the factory. Installing the switch includes the following procedures: • Mounting the enclosure. • Installing the circuit breakers. • Connecting power source and load leads. • Connecting the generator control wiring. • Connecting branch circuit wiring. 3.2 — Mounting Mounting dimensions for the transfer switch enclosure are in this manual. Enclosures are typically wallmounted.
Installation 1. Install a 2-pole, 100 Amp breaker in the main distribution panel. This will be the utility (normal) power source for transfer switch. 2. Install a conduit between the main distribution panel and transfer switch enclosures. 3. Run connections from 2-pole, 100 Amp breaker through conduit. 4. Connect utility (normal) power source cables to N1 and N2 terminals on the transfer switch mechanism. 5. Connect the generator (standby) source power cables to transfer switch terminals E1, E2.
Installation 2. Remove the ungrounded (hot) conductor from the circuit breaker and neutral conductor from the neutral terminal bar in the normal power panel board. NOTE: If the circuit to be protected is part of a multi-wire branch circuit, the entire multi-wire branch circuit has to be relocated to the transfer switch panel board. 3.
Installation This page intentionally left blank.
Section 4 Operation 4.1 — Functional Tests and Adjustments • Manual operation handle in the DOWN position LOAD terminals (T1, T2) are connected to EMERGENCY terminals (E1, E2). Following transfer switch installation and interconnection, inspect the entire installation carefully. A competent, qualified electrician should inspect it. The installation should comply strictly with all applicable codes, standards, and regulations.
Operation 4.2.3— Return to Utility Source Side 1. Manually actuate switch to return manual operating handle to the UP position. 2. Remove manual operating handle from movable contact carrier arm. Return handle to storage bracket. 4.3 — Voltage Checks Turn ON the UTILITY power supply to the transfer switch using the breaker in main distribution panel. DANGER Electrocution. High voltage is present at transfer switch and terminals. Contact with live terminals will result in death or serious injury.
Operation NOTE: See “Manual Operation”. Handle and operating lever of transfer switch should be in up position. 9. Turn on the utility power supply to transfer switch, using whatever means provided (such as a utility main line circuit breaker). The utility power source now powers the loads. 10. The system is now set for fully automatic operation. 4.5 — Checking Automatic Operation To check the system for proper automatic operation, proceed as follows: 1. Verify generator is in OFF mode. 2.
Operation This page intentionally left blank.
=@A5=AGF EG;F34>7 8AD # #!$ $ 5A@6G;F E;L7 $ B>357E #)' &__ M( +# O Automatic Transfer Switch Owner’s Manual B36>A5= 5GEFA?7D EGBB>;76 >A53F;A@ )(& %__ M%" # O =@A5=AGF EG;F34>7 8AD %!& # 5A@6G;F E;L7 % *__ M#% ' O =@A5=AGF EG;F34>7 8AD # #!$ $ 5A@6G;F E;L7 $ B>357E &$ &__ M# ) O FKB;53> ()+ &'__ M$( )' O & "$__ M" $ O %) '__ M# &* O FKB;53> ĵ#&__ Mĵ" ( O ) &*__ M" % O ĵ*__ Mĵ" % O Section 5 =@A5=AGF EG;F34>7 8AD # #!$ $ 5A@6G;F E;L7 $(( )__ M#" ' O Drawings and Diagram
Drawings and Diagrams 5.2 — Interconnection Drawing 5.2.1— Drawing No.
Drawings and Diagrams 5.2.2— Drawing No.
Part No. 0L0324 Rev. A 02/26/15 Printed in USA ©2015 Generac Power Systems, Inc. All rights reserved Specifications are subject to change without notice. No reproduction allowed in any form without prior written consent from Generac Power Systems, Inc. Generac Power Systems, Inc. S45 W29290 Hwy. 59 Waukesha, WI 53189 1-888-GENERAC (1-888-436-3722) generac.