Owner's Manual

Owner’s Manual for Power Zone Connectivity Server 45
Troubleshooting
Section 4 Troubleshooting
Troubleshooting Guide
Problem Solution
Red LED in front of
enclosure is OFF
Verify 12 V power and ground wires are connected properly on PWR_RS485 connector to
the Power Zone Pro Main Controller BS6 connector.
Green LED in front
of enclosure is OFF
Verify the RS-485 wires are connected properly on PWR_RS485 connector to the Power
Zone Pro Main Controller BS6 Connector.
Green LED in front
of enclosure is not
blinking
Operating system or application is not working properly. Unplug and plug back the
PWR_RS485 cable to the Connectivity Server.