Manual

2.2 HOURIVIETER
TheHourmetertrackshoursof operationfor scheduledmaintenance
(Figure5):
Therewill be a "CHGOIL"messageevery100 hours.The message
will flash one hour before and one hour after each 100 hour
interval, providing atwo hourwindow to perform service.
This messagewill actually beginflashing at 99 hours and disable
itself at 101 hours again,providing atwo hourwindow to perform
the service.
Every200 hours the "SVC"icon on the lower left hand corner of
the display will flash. The messagewill flash one hourbefore and
onehourafter each 200 hourintervalprovidingatwo hourwindow
to perform service.
Whenthe hour meter is inthe FlashAlert mode, the maintenance
message will always alternate with elapsed time in hours and
tenths. The hours wilt flash four times, then alternate with the
maintenancemessagefour times until the meter resets itself.
100 hours - CHGOIL-- Oil ChangeInterval(Every100 hrs)
200 hours - SVC-- ServiceAir Filter(Every200 hrs)
Note:
The hour glassgraphicwill flash on and off when the engine
is running.This signifiesthat the meter is tracking hours of
operation.
Figure 5 - Hourmeter
0000.0
,
HOURGLASS RESETBUTTON
GRAPHIC (IF EQUIPPED)
2.3 CORDSETSANDCONNECTIONPLUGS
2.3.1 120VAC,20 AMP,DUPLEXRECEPTACLE
This is a 120 Volt outlet protectedagainst overloadby a 20 Amp
push-to-resetcircuit breaker (Figure6). Useeach socketto power
120 Volt AC, single phase,60 Hzelectrical loads requiringupto a
combined 2400 watts (2.4 kW) or 20 Amps of current. Useonly
high quality, well-insulated, 3-wire grounded cord sets rated for
125 Volts at 20 Amps (or greater).
Keep extensioncords as short as possible, preferablyless than
15 feet long, to preventvoltage drop and possibleoverheatingof
wires.
Figure 6 - 120 Volt AC, 20 Amp, Duplex Receptacle
D
2.3.2 120/240VAC,30 AMPRECEPTACLE
Use a NEMA L14-30 plug with this receptacle (rotate to lock!
unlock). Connecta suitable4-wire groundedcord set to the plug
andto the desiredtoad.The cord set should be ratedfor 250 Volts
AC at 30 Amps (or greater) (Figure7).
Figure 7 - 120/240 VAC, 30 Amp Receptacle
12OV/24OV
3CA
Use this receptacleto operate 120 Volt AC, 60 Hz, single phase
loads requiringup to 3600 watts (3.6 kW) of power at 30 Amps or
240 Volt AC,60 Hz, singlephase loads requiringup to 7200 watts
(7.2 kW) of power at 30 Amps. The outlet is protectedby two 30
Amp push-to-resetcircuit breakers.
2.3.3 120VAC,20 AMP,GFC/OUPLEXRECEPTACLE
This is a 120 Volt outlet protectedagainst overloadby a 20 Amp
push-to=resetcircuit breaker (Figure8). Useeach socketto power
120 Volt AC, single phase,60 Hzelectrical loads requiringup to a
combined 2400 watts (2.4 kW) or 20 Amps of current. Use only
high quality, well-insulated, 3-wire grounded cord sets rated for
125 Volts at 20 Amps (or greater).
Keepextensioncords as short as possibleto preventvoltagedrop
and possibleoverheatingof wires.