Installation Manual

1
INDOOR MANUAL TRANSFER SWITCHES
For Models 200660, 300660, 301660, 301060, 501210
INSTALLATION AND OPERATING INSTRUCTIONS
Warning: Gen/Tran transfer switches should be installed by a professional electrician familiar with electrical wiring and codes, and experienced in working with generators.
Gen/Tran accepts no responsibility for accidents, damages or personal injury caused by incorrect installation. These transfer switches are intended for surface or flush mounting
INDOORS only.
Caution: If using the generator and transfer switch for larger appliances, such as electric water heaters, clothes dryers, electric ranges and air conditioners, verify the appliances
to be sure they do NOT exceed the amperage rating of the generator. No one appliance can have an amperage rating that exceeds the transfer switch “GENERATOR MAIN” rating.
Note: This transfer switch will not operate properly with neutral-bonded generators unless the generator neutral-bonding feature is disabled or the optional Gen/Tran Switched
Neutral Kit (Model: SNK) is installed. Consult your generator manufacturer for directions to disable the neutral-bonding feature.
Note to Installer: Please leave this manual with the consumer for future reference.
Una versión en español de este manual está disponible para descargar en nuestra página web www.gen-tran.com/support/installation
Thank you for purchasing the most versatile manual transfer switch available today. Gen/Tran’s PowerStay
®
Manual Transfer Switches are designed to safely
connect generators and renewable energy sources to load centers in homes and light commercial buildings (single phase only) for backup power applications.
Features include:
NEW: This switch accommodates AFCI and GFCI circuit breakers (optional, available from Gen/Tran)
NEW: Sufficient ground and neutral termination positions for all branch circuits
NEW: Expand beyond 16 circuits using sub-feed lugs and adding a sub-panel
NEW: Accommodates neutral-bonded generators when SNK option is installed
Generator Main and Utility Main are mechanically interlocked preventing utility or
generator back feed
Full branch circuit protection with Siemens
®
circuit breakers
Dual wattmeters help monitor and balance generator load, prolonging generator life
Pre-assembled wire harness for easy connection to the load center
What is included in this carton:
A: Manual transfer switch for 6, 10 or 12 circuits
B: Wire harness, pre-assembled
C: Flexible non-metallic conduit (21.5”) and fittings (2)
D: Wire connectors (6, 10 or 12)
E: Male Flanged Power Inlet
F: Installation manual and Warranty Card
Tools Needed for Installation:
¼” nut driver, 2-1/8” hole saw (if flush mounting)
Screwdrivers, straight blade and Phillips
Electric drill, drill bits, wallboard saw
Wire cutter/stripper
Safety eye goggles
Other Items Needed for Installation:
New 2-pole, 240V Breaker to mount in main load center – amperage to match utility breaker (see specifications Table I for Utility Main Breaker size – should be
manufactured by same as Main load center).
Anchors and screws to mount switch to wall
Optional Items for Installation:
Arc-fault, GFCI or Surge protection circuit breakers. If AFCI, GFCI or Surge protection circuit breakers are used as the branch circuit protector in the main load center,
they MUST be used in the manual transfer switch. You may be able to re-use your existing AFCI, GFCI and Surge protection circuit breakers in the manual transfer
switch. See above for compatible breakers. (Available through Gen/Tran).
Power Inlet Box – for “hard-wired” installations. See TABLE 1. (Available through Gen/Tran).
Wire, fittings and conduit to connect the Power Inlet Box to the transfer switch
Power Cord to connect generator to transfer switch or Power Inlet Box. (Available through Gen/Tran).
White, green, black and red THHN or MTW wire, 6 or 10 AWG, 300V rated (if breaker configuration is modified or expanded)
Switched Neutral Kit (Model SNK) to accommodate neutral-bonded generators and local codes requiring neutral switching during generator use
TABLE 1 - SPECIFICATIONS:
MODEL # 200660 300660** 301660 301060 501210
# Circuits Provided 6 6 6 10 12
UTILITY MAIN circuit breaker 60 Amp 60 Amp 60 Amp 60 Amp 100 Amp
GEN MAIN circuit breaker 20 Amp 20 Amp 30 Amp 30 Amp 60 Amp
Max Load per Circuit As marked As marked As marked As marked As marked
Max Load Combined 20 Amp 30 Amp 30 Amp 30 Amp 60 Amp
Max Watts @ 240 Volt 5000 N/A 7500 7500 15,000
Max Watts @ 120 Volt 5000 3750 7500 7500 15,000
Max 1-pole Circuits * 16 16 16 16 16
Max 2-pole Circuits * 8 0 8 8 8
Power Inlet Kit (included) FI-1420 FI-530 FI-1430 FI-1430 FI-6365
Power Inlet Box (optional) 14202/14203/1420V 53002
/
53003
/
530V 14302/14303
/
1430V 14302/14303/1430V 63652/63653
/
6365V
Min. gauge Cord Size 12/4 AWG 10/3 AWG 10/4 AWG 10/4 AWG 6/4 AWG