Full Product Manual

Operation
20 Synergy Automatic Standby Generator Owner’s Manual
Figure 3-4. Manual Transfer Switch Operation (Typical)
6. Turn on the utility power supply to the transfer switch using the means provided.
7. Press AUTO on the control pad. A green LED illuminates to confirm that the system is in the AUTO mode.
3.9 — Removal From Service During Utility Outages
If, during prolonged utility outages, the user wishes to remove the unit from service to conserve fuel, reduce run hours,
or to perform maintenance tasks, then complete the steps listed below.
IMPORTANT NOTE: Failure to abide by this procedure can result in equipment damage.
To remove the generator from service while running in AUTO and online, proceed as follows:
1. Turn the main utility disconnect to OFF (Open).
2. Move the Generator Disconnect Circuit Breaker switch to the OFF (Open) position.
3. Allow unit to cool for one minute.
4. Press OFF on the control pad to shut down the engine.
NOTE: If the generator is to remain off for more than an hour with utility power NOT PRESENT, wait one hour
for the internal fans to cool it down.
5. Pull up rubber flap covering fuse holder and remove 7.5 amp fuse to prevent discharge of the starting battery.
To return the generator to service, proceed as follows:
1. Pull up rubber flap covering fuse holder and install 7.5 amp fuse.
2. Follow Install Wizard and enter information as required.
3. Press AUTO on the control pad. A green LED illuminates to confirm that the system is in the AUTO mode. Allow
the generator to start and run for 20 seconds.
4. Move the Generator Disconnect Circuit Breaker switch to the ON (Closed) position.
5. Turn the main utility disconnect to ON (Closed).
Manual Transfer
Handle
Transfer Switch
Operating Lever
Load Connected to Utility
Load Connected to Standby