Replacement Part List

10 of 11
Protector
®
Series
60 kW installation layout
Drawing #0L2090-B (1 of 2)
357
[14.0]
167
[6.6]
683.3 [26.9]
CENTER OF GRAVITY
50 [2.0]
1000 [39.4]
1170
[46.1]
OVERALL
HEIGHT
888 [35.0]
OVERALL WIDTH
58
[2.3]
TYP
1857 [73.1]
1950 [76.8]
OVERALL LENGTH
758 [29.8]
DOOR TYP
SERVICE ITEM 2.4L
OIL FILL CAP EITHER SIDE
OIL DIP STICK RIGHT SIDE
OIL FILTER LEFT SIDE
OIL DRAIN HOSE RIGHT SIDE
RADIATOR DRAIN HOSE LEFT SIDE
COOLANT RECOVERY BOTTLE LEFT SIDE
RADIATOR FILL CAP ROOF TOP
AIR CLEANER ELEMENT LEFT SIDE
SPARK PLUGS LEFT SIDE
MUFFLER SEE NOTE 11
DRIVE BELT EITHER SIDE
FAN BELT SEE NOTE 11
BATTERY LEFT SIDE
LUBE OIL MAINTAINER
SUPPLY TANK FILL CAP
ROOF TOP
WEIGHT DATA
ENGINE/KW
ENCLOSURE
MATERIAL
WEIGHT
GENSET ONLY
KG [LBS]
WEIGHT
SHIPPING SKID
KG [LBS]
SHIPPING WEIGHT
KG [LBS]
2.4L 60KW ST 582 [1283] 44 [98] 626 [1381]
2.4L 60KW AL 558 [1230] 44 [98] 602 [1328]
NOTES:
1. MINIMUM RECOMMENDED CONCRETE PAD SIZE: 1194MM (47") WIDE X 2256MM (88.8") LONG.
REFERENCE INSTALLATION GUIDE SUPPLIED WITH UNIT FOR CONCRETE PAD GUIDELINES.
2. ALLOW SUFFICIENT ROOM ON ALL SIDES OF THE GENERATOR FOR MAINTENANCE
AND SERVICING. THIS UNIT MUST BE INSTALLED IN ACCORDANCE WITH CURRENT
APPLICABLE NFPA 37 AND NFPA 70 STANDARDS AS WELL AS ANY OTHER FEDERAL,
STATE, AND LOCAL CODES.
3. CONTROL PANEL / CIRCUIT BREAKER INFORMATION:
- SEE SPECIFICATION SHEET OR OWNERS MANUAL
- ACCESSIBLE THROUGH CUSTOMER ACCESS ASSEMBLY DOOR ON REAR OF GENERATOR.
4. REMOVE THE REAR ENCLOSURE COVER PANEL TO ACCESS
THE STUB-UP AREAS AS FOLLOWS:
- HIGH VOLTAGE CONNECTION INCLUDING AC LOAD LEAD CONDUIT CONNECTION
NEUTRAL CONNECTION, BATTERY CHARGER 120 VOLT AC (0.5 AMP MAX) CONNECTION.
- LOW VOLTAGE CONNECTION INCLUDING TRANSFER SWITCH CONTROL WIRES.
5. CENTER OF GRAVITY AND WEIGHT MAY CHANGE DUE TO UNIT OPTIONS.
6. BOTTOM OF GENERATOR SET MUST BE ENCLOSED TO PREVENT PEST INTRUSION AND
RECIRCULATION OF DISCHARGE AIR AND/OR IMPROPER COOLING AIR FLOW.
7. REFERENCE OWNERS MANUAL FOR LIFTING WARNINGS.
8. MOUNTING BOLTS OR STUDS TO MOUNTING SURFACE SHALL BE 5/8-11 GRADE 5
(USE STANDARD SAE TORQUE SPECS)
9. MUST ALLOW FREE FLOW OF INTAKE AIR, DISCHARGE AIR AND EXHAUST. SEE SPEC
SHEET FOR MINIMUM AIR FLOW AND MAXIMUM RESTRICTION REQUIREMENTS.
10. GENERATOR MUST BE INSTALLED SUCH THAT FRESH COOLING AIR IS AVAILABLE
AND THAT DISCHARGE AIR FROM RADIATOR IS NOT RECIRCULATED.
11. EXHAUST MUFFLER AND FAN BELT ENCLOSED WITHIN GENERATOR ENCLOSURE,
REMOVE FRONT PANEL TO ACCESS.
REFERENCE OWNERS MANUAL
FOR PERIODIC REPLACEMENT
PART LISTINGS.
RIGHT SIDE VIEW
REAR VIEW
LEFT SIDE VIEW
TOP VIEW
DIMENSIONS: MM [INCH]
RADIATOR/EXHAUST
DISCHARGE AIR
EXHAUST MUFFLER
ENCLOSED WITHIN
GENERATOR ENCLOSURE
FUEL LINE CONNECTION
3/4" NPT FEMALE COUPLING
CIRCUIT BREAKER
SEE NOTE 3
REAR ENCLOSURE
COVER PANEL
SEE NOTE 4
CUSTOMER ACCESS
ASSEMBLY, CONTROL
PANEL ACCESS,
BATTERY CHARGER
LOCATED WITHIN
SEE NOTE 4
VICE ACTION LATCH,
ONE PER DOOR,
ONE LIFT OFF
DOOR PER SIDE
OF GENERATOR
RADIATOR/EXHAUST
DISCHARGE AIR
(BOTH SIDES)
AIR INTAKE
(BOTH SIDES)
BATTERY 12V
GROUP 26
NEGATIVE GROUND
P/N: 077483
REMOVE COVER
FOR ACCESS TO
RADIATOR FILL CAP
REMOVE COVER FOR
ACCESS TO LUBE OIL
MAINTAINER SUPPLY TANK
REFERENCE OWNERS MANUAL