Replacement Part List

3 of 11
25 • 30 • 36 • 45 • 60 kW operating data
GENERATOR OUTPUT VOLTAGE/kW - 60 Hz
kW LPG Amp LPG kW Nat. Gas Amp Nat. Gas CB Size (Both)
RG025
120/240 V, 1Ø, 1.0 pf 25 104 25 104 125
120/208 V, 3Ø, 0.8 pf 25 87 25 87 100
120/240 V, 3Ø, 0.8 pf 25 75 25 75 90
RG030
120/240 V, 1Ø, 1.0 pf 30 125 30 125 150
120/208 V, 3Ø, 0.8 pf 30 104 30 104 125
120/240 V, 3Ø, 0.8 pf 30 90 30 90 100
RG036
120/240 V, 1Ø, 1.0 pf 36 150 36 150 175
120/208 V, 3Ø, 0.8 pf 36 125 36 125 150
120/240 V, 3Ø, 0.8 pf 36 108 36 108 125
277/480 V, 3Ø, 0.8 pf 36 54 36 54 60
RG045
120/240 V, 1Ø, 1.0 pf 45 188 45 188 200
120/208 V, 3Ø, 0.8 pf 45 156 45 156 175
120/240 V, 3Ø, 0.8 pf 45 135 45 135 150
277/480 V, 3Ø, 0.8 pf 45 68 45 68 80
RG060
120/240 V, 1Ø, 1.0 pf 60 250 60 250 300
120/208 V, 3Ø, 0.8 pf 60 208 60 208 250
120/240 V, 3Ø, 0.8 pf 60 180 60 180 200
277/480 V, 3Ø, 0.8 pf 60 90 60 90 100
SURGE CAPACITY IN AMPS
Voltage Dip @ < .4 pf
15% 30%
RG025
120/240 V, 1Ø 65 170
120/208 V, 3Ø 80 130
120/240 V, 3Ø 69 112
RG030
120/240 V, 1Ø 75 180
120/208 V, 3Ø 96 155
120/240 V, 3Ø 83 134
RG036
120/240 V, 1Ø 105 240
120/208 V, 3Ø 44 130
120/240 V, 3Ø 38 115
277/480 V, 3Ø 20 60
RG045
120/240 V, 1Ø 105 240
120/208 V, 3Ø 44 130
120/240 V, 3Ø 38 115
277/480 V, 3Ø 20 60
RG060
120/240 V, 1Ø 140 320
120/208 V, 3Ø 70 210
120/240 V, 3Ø 61 182
277/480 V, 3Ø 30 91
ENGINE FUEL CONSUMPTION
Natural Gas Propane
(ft³/hr) (m³ /hr) (gal/hr) (l/hr) (ft³/hr)
RG025
Exercise cycle 60 1.7 0.7 2.5 24
25% of rated load 220 6.3 2.9 9.1 88
50% of rated load 297 8.4 3.3 12.3 119
75% of rated load 362 10.3 4 15 145
100% of rated load 430 12.2 4.7 17.8 172
RG030
Exercise cycle 60 1.7 0.7 2.5 24
25% of rated load 240 6.8 2.6 10 96
50% of rated load 320 9.1 3.5 13.3 128
75% of rated load 400 11.4 4.4 16.6 160
100% of rated load 492 14 5.4 20.4 197
RG036
Exercise cycle 65 1.8 0.7 2.6 25
25% of rated load 210 6 2.3 8.6 83
50% of rated load 380 10.8 4.2 15.7 151
75% of rated load 545 15.5 5.9 22.4 216
100% of rated load 730 20.7 8 30.1 290
RG045
Exercise cycle 65 1.8 0.7 2.6 25
25% of rated load 210 6 2.3 8.6 83
50% of rated load 380 10.8 4.2 15.7 151
75% of rated load 545 15.5 5.9 22.4 216
100% of rated load 730 20.7 8 30.1 290
RG060
Exercise cycle 123 3.5 1.34 5.1 49.3
25% of rated load 267 7.6 2.7 10.5 101
50% of rated load 483 13.7 5 19 183
75% of rated load 672 19.1 7 26.5 255
100% of rated load 862 24.5 9 33.9 327
Protector
®
Series
STANDBY RATING: Standby ratings apply to installations served by a reliable utility source. The standby rating is applicable to varying loads for the duration of a power outage. There
is no overload capability for this rating. Ratings are in accordance with ISO-3046-1. Design and specifications are subject to change without notice.
Note: Fuel pipe must be sized for full load.
For Btu content, multiply ft³/hr x 2520 (LP) or ft³/hr x 1000 (NG)
For megajoule content, multiply m³/hr x 93.15 (LP) or m³/hr x 37.26 (NG)
Refer to "Emissions Data Sheets" for maximum fuel flow for EPA and
SCAQMD permitting purposes.