Full Product Manual

Operation
Owner’s Manual for 60 Hz Air-Cooled Generators 13
Control Panel Interface
See Figure 3-5. The control panel interface (A) is located
under the lid of the enclosure. Verify that both the left and
right side locks are unlocked before attempting to lift the
lid of the enclosure. Open the lid as directed in Opening
the Lid.
The 7.5A fuse is located beneath the rubber cover (B) to
the right of the control panel.
Verify that both the left and right side locks are securely
out of the way before closing the unit.
Figure 3-5. Generator Control Panel
All appropriate panels must be in place during any
operation of the generator. This includes operation by a
servicing technician while conducting troubleshooting
procedures.
Using the AUTO/OFF/MANUAL
Interface
NOTE: Damage caused by mis-wiring of the
interconnect wires is not warrantable.
Interface Menu Displays
The LCD Panel
Button Description of Operation
AUTO
This button activates fully automatic system
operation. It allows the unit to automatically
start and exercise the generator according to
the exercise timer (see Setting the Exercise
Timer
).
The Green LED on this button will flash if
running in Automatic mode and the connected
loads are running under generator power (utility
is lost).
OFF
This button shuts down the engine and
prevents automatic operation of the unit.
MANUAL
This button cranks and starts the generator.
Transfer to standby power will not occur unless
there is a utility failure.
The blue LED on this button will flash if running
in manual mode and the connected loads are
running under generator power (utility is lost).
001798
A
B
Feature Description
HOME
page
Default page that is displayed if no buttons are
pressed for 60 seconds. Normally shows
current status message and the current date
and time. The highest priority active alarm/
warning is automatically posted on this page,
as well as flashing the backlight when such a
condition is detected. In the case of multiple
alarms/warnings, only the first message will be
displayed. Press the OFF button and then
press the ENTER button to clear an alarm or
warning.
Display
Backlight
Normally off. The backlight will automatically
light and remain on for 30 seconds if the
operator presses any button.
MAIN
MENU
page
Allows the operator to navigate to all other
pages or sub-menus by using the arrow keys
and the ENTER button. Page can be accessed
at any time with several presses of the
dedicated ESCAPE button. Each press of the
ESCAPE button takes the operator to the
previous menu until the MAIN MENU displays.
This page contains information for - History;
Status; Edit; Debug.