® Installation Guidelines 60 Hz Air-Cooled Generators 10 kW to 24 kW WARNING Loss of life. This product is not intended to be used in a critical life support application. Failure to adhere to this warning could result in death or serious injury. (000209b) Register your Generac product at: WWW.GENERAC.COM 1-888-GENERAC (888-436-3722) Para español, visita: http://www.generac.com/service-support/product-support-lookup Pour le français, visiter : http://www.generac.
Use this page to record important information about this generator. Record the information found on the unit data label on this page. For location of the unit data label, see owner’s manual. Model: The unit has a label plate affixed to the inside partition, to the left of the control panel console. Serial: Always supply the complete model and serial numbers of the unit when contacting an Independent Authorized Service Dealer (IASD) about parts and service.
Table of Contents Section 1: Safety Rules & General Information Proximity to Utilities ..................................................17 Verify Wi-Fi Range ....................................................17 Introduction ..................................................................1 Read This Manual Thoroughly ....................................1 Transportation Recommendations ..........................17 Suitable Mounting Surface ........................................17 Safety Rules .....
Table of Contents Section 7: Control Panel Startup / Testing Control Panel Interface ............................................. 33 Using the AUTO/OFF/MANUAL Buttons .................. 33 Generator Setup ........................................................ 33 Activation .................................................................. 33 Cold Smart Start ....................................................... 35 Setting The Exercise Timer .......................................
Safety Rules & General Information Section 1: Safety Rules & General Information Introduction Safety Rules Thank you for purchasing this compact, high performance, air-cooled, engine-driven generator. It is designed to automatically supply electrical power to operate critical loads during a utility power failure. This unit is factory installed in an all-weather, metal enclosure intended exclusively for outdoor installation.
Safety Rules & General Information General Hazards WARNING DANGER Loss of life. Property damage. Installation must always comply with applicable codes, standards, laws and regulations. Failure to do so will result in death or serious injury. (000190) DANGER Automatic start-up. Disconnect utility power and render unit inoperable before working on unit. Failure to do so will result in death or serious injury. (000191) WARNING Electrocution. Potentially lethal voltages are generated by this equipment.
Safety Rules & General Information Exhaust Hazards DANGER Asphyxiation. Running engines produce carbon monoxide, a colorless, odorless, poisonous gas. Carbon monoxide, if not avoided, will result in death or serious injury. (000103) DANGER Asphyxiation. Carbon monoxide can kill in minutes. Operate this unit outdoors only. Failure to do so will cause death or serious injury. (000525) WARNING Equipment and property damage. Do not alter construction of, installation, or block ventilation for generator.
Safety Rules & General Information Battery Hazards WARNING Electrocution. Refer to local codes and standards for safety equipment required when working with a live electrical system. Failure to use required safety equipment could result in death or serious injury. (000257) WARNING Risk of Fire. Unit must be positioned in a manner that prevents combustible material accumulation underneath. Failure to do so could result in death or serious injury.
Safety Rules & General Information General Rules • Fully comply with all relevant NEC, NFPA, and DANGER Loss of life. Property damage. Installation must always comply with applicable codes, standards, laws and regulations. Failure to do so will result in death or serious injury. (000190) DANGER Electrical backfeed. Use only approved switchgear to isolate generator from the normal power source. Failure to do so will result in death, serious injury, and equipment damage.
Safety Rules & General Information 8. NFPA 70E: Standard For Electrical Safety In The Workplace * 9. NFPA 110: Standard for Emergency and Standby Power Systems * 10. NFPA 211: Standard for Chimneys, Fireplaces, Vents, and Solid Fuel Burning Appliances * 11. NFPA 220: Standard on Types of Building Construction * 12. NFPA 5000: Building Code * 13. International Building Code ** 14. Agricultural Wiring Handbook *** 15. Article X, NATIONAL BUILDING CODE 16. ASAE EP-364.
Unpacking and Inspection Section 2: Unpacking and Inspection General Unpacking NOTE: Carefully inspect contents for damage after unpacking. Unpack and inspect unit immediately upon delivery to identify any damage which may have occurred in transit. Any claims for shipping damage must be filed as soon as possible with freight carrier. This is especially important if unit will not be installed for a period of time. Proceed as follows to unpack the generator: 1. Remove outer shipping carton. 2.
Unpacking and Inspection IMPORTANT NOTE: DO NOT perform next step until generator has been transported to installation site. 4. See Figure 2-3. Remove bolts and pallet brackets (A). Exercise caution when removing generator. Dragging it off pallet will damage base. The unit must be lifted from wooden pallet to remove. NOTE: Bolts and pallet brackets are provided only for shipping purposes and can be discarded after removal.
Unpacking and Inspection Intake Side Panel Removal See Figure 2-6. The intake side panel (A) must be removed to access battery compartment, fuel regulator, and sediment trap. 1. Raise lid and remove front panel. 2. Use a hex key to remove two mounting screws (B) and the hex screw (C) on the L-bracket. 3. Lift intake panel up and away from generator. 4. Inspect for any hidden freight damage. Contact freight carrier if damage is present.
Unpacking and Inspection Main Line Circuit Breaker (Generator Disconnect) Parts Shipped Loose A See Figure 2-9. The 2-pole main line circuit breaker (MLCB) (generator disconnect) (A) is rated according to relevant specifications. E B C D 001803 B A 001810 Figure 2-9. Generator Main Line Circuit Breaker Generator MLCB (generator disconnect) can be locked in OFF (OPEN) position for security during maintenance or transfer switch service.
Unpacking and Inspection Auxiliary Shutdown Switch CAUTION Equipment Damage. The auxiliary shutdown switch is not to be used to power down the unit under normal operating circumstances. Doing so will result in equipment damage. (000399) All generators are equipped with an external means of shutting down the generator which complies with the latest NEC code requirement. The primary generator shutdown sequence is described in Control Panel Startup / Testing. See Figure 2-11.
Unpacking and Inspection This page intentionally left blank.
Site Selection and Preparation Section 3: Site Selection and Preparation Site Selection Site selection is critical for safe generator operation. It is important to discuss these factors with the installer when selecting a site for generator installation: • • • • • • Carbon monoxide Fire prevention Fresh air for ventilation and cooling Water ingress prevention Proximity to utilities Suitable mounting surface The following pages describe each of these factors in detail.
Site Selection and Preparation Potential CO Entry Points Protect the Structure See Figure 3-1. Generator exhaust can enter a structure through large openings, such as windows and doors. However, exhaust and CO can also seep into the structure through smaller, less obvious openings. Verify structure itself is correctly caulked and sealed to prevent air from leaking in or out. Voids, cracks, or openings around windows, doors, soffits, pipes, and vents can allow exhaust gas to be drawn into the structure.
Site Selection and Preparation Fire Prevention The generator must be installed at a safe distance away from combustible materials. Engine, alternator, and exhaust system components become very hot during operation. Fire risk increases if unit is not correctly ventilated, is not correctly maintained, operates too close to combustible materials, or if fuel leaks exist. Also, accumulations of flammable debris within or outside the generator enclosure may ignite. Distance Requirements See Figure 3-2.
Site Selection and Preparation Fire Codes, Standards, and Guidelines Generator installation must comply strictly with ICC IFGC, NFPA 37, NFPA 54, NFPA 58, and NFPA 70 standards. These standards prescribe the minimum safe clearances around and above the generator enclosure. NFPA 37 NFPA 37 is the The National Fire Protection Association’s standard for the installation and use of stationary combustion engines.
Site Selection and Preparation Fresh Air for Ventilation and Cooling Suitable Mounting Surface Install unit where air inlet and outlet openings will not become obstructed by leaves, grass, snow, etc. If prevailing winds will cause blowing or drifting, consider using a windbreak at a safe distance to protect the unit. See Figure 3-4. Prepare a rectangular area approximately 5 in (127 mm) deep (A) and approximately 3 in (76.2 mm) longer and wider (B) than the generator on all sides.
Site Selection and Preparation This page intentionally left blank.
Generator Placement Section 4: Generator Placement Generator Placement See Figure 4-1. All air-cooled generators come with a composite pad. This composite pad elevates the generator and helps prevent water from pooling around base. Three mounting holes are available if codes require securing generator to concrete. Mounting holes are located inside the generator compartment—two in front and one in back. Three 3/8 in (or M10) lag bolts (not supplied) are recommended for securing generator to a concrete pad.
Generator Placement This page intentionally left blank.
Fuel Conversion / Gas Connections Section 5: Fuel Conversion / Gas Connections Fuel Requirements and Recommendations DANGER Explosion and fire. Fuel and vapors are extremely flammable and explosive. No leakage of fuel is permitted. Keep fire and spark away. Failure to do so will result in death or serious injury. (000192) NOTE: NG is lighter than air and will collect in high areas. LP gas is heavier than air and will settle in low areas. LP gas should only use a vapor withdrawal system.
Fuel Conversion / Gas Connections Fuel Consumption Generator Natural Gas* Propane** 1/2 Load Full Load 1/2 Load Full Load 10 kW 2.86 / 101 3.60 / 127 0.97 / 3.66 / 36 1.48 / 5.62 / 54 14 kW 5.52 / 195 7.25 / 256 1.81 / 6.87 / 65 3.07 / 11.61 / 112 18 kW 4.79 / 169 6.99 / 247 1.70 / 6.45 / 62 3.02 / 11.44 / 110 20 kW 4.64 / 164 8.13 / 287 2.36 / 8.95 / 86 3.74 / 14.15 / 136 22/24 kW 5.75 / 203 8.66 / 306 2.53 / 9.57 / 92 3.90 / 14.
Fuel Conversion / Gas Connections Natural Gas Pipe Sizing NOTE: See Table B.3.2 in NFPA 54 or Table A.2.2 in the ICC IFGC, Equivalent Lengths of Pipe Fittings and Valves for the correct values to be added to overall fuel piping length. Tables are based on schedule 40 black pipe. If installing any other piping system, follow pipe sizing charts for selected piping system. To determine correct NG pipe size, find the kW rating of generator in the left column, and trace to the right.
Fuel Conversion / Gas Connections Installing and Connecting Fuel Lines . DANGER Explosion and fire. Fuel and vapors are extremely flammable and explosive. No leakage of fuel is permitted. Keep fire and spark away. Failure to do so will result in death or serious injury. (000192) IMPORTANT NOTE: NG and LP gas are highly volatile substances. Strictly adhere to all safety procedures, codes, standards, and regulations. Fuel line connections should be made by a certified contractor familiar with local codes.
Fuel Conversion / Gas Connections Checking Fuel Line Connections Performing Fuel System Leak Test Checking Fuel Pressure Proceed as follows to check fuel pressure at fuel regulator in the generator. 1. Close fuel supply valve. 2. See Figure 5-4. Remove top fuel pressure test port from fuel regulator and install fuel pressure tester (manometer). DANGER Explosion and fire. Fuel and vapors are extremely flammable and explosive. No leakage of fuel is permitted. Keep fire and spark away.
Fuel Conversion / Gas Connections Natural Gas Installation (Typical) A D F E I C B G H J 008965 NG BTU/h = ft3/h X 1000 Megajoules/h = m3/h X 37.26 A Fuel data decal B Minimum distance from rear obstruction—see Distance Requirements C Manual fuel shutoff valve (pressure port optional) Must be located no more than 6 ft (1.83 m) away from fuel inlet D Pipe fittings (field supplied) E Flexible fuel line F Verify clearance with gas provider. Regulator should be a minimum of 5 ft (1.
Fuel Conversion / Gas Connections LP Gas (Vapor) Installation (Typical) A D E J L H G K C B F 008966 LPG BTU/h = ft3/h X 2500 Megajoules/h = m3/h X 93.15 A Fuel data decal B Minimum distance from rear obstruction—see Distance Requirements C Manual fuel shutoff valve (pressure port optional) Must be located no more than 6 ft (1.83 m) away from fuel inlet.
Fuel Conversion / Gas Connections This page intentionally left blank.
Electrical Connections Section 6: Electrical Connections Generator Connections See Figure 6-1. The electrical wiring enclosure is located behind an access panel on intake end of unit. Remove intake side panel as directed in Intake Side Panel Removal, and then remove access panel. Connect wires according to diagram and tables. 1. Remove main AC / control wiring knock-out plugs from back of generator. 2.
Electrical Connections Control Wiring B A C1 1 1 1 0 1 DC GROUND 2 194 2 2 0 1 1 DC GROUND 2 194 1 1 2 N1 UTILITY SENSE N2 3 T1 VAC LOAD 3 SUPPLY 2 + 12 VDC 3 23 3TRANSFER E1 C2 N1 UTILITY SENSE N2 E2 2 + 12 VDC 2 3 23 3TRANSFER 3 T1 VAC LOAD 3 SUPPLY 005810 J H D F G Figure 6-1. Electrical Wiring Connections Table 6-1.
Electrical Connections . Table 6-4. Ground and Neutral Connections (Copper or Aluminum Conductors) See national and/or local codes to verify correct wire sizes. No. Description Recommended Wire Size Torque Spec 1 Power wire terminals 2/0 to 8 AWG 120 in-lbs (13.56 Nm) 2 Large neutral lug 2/0 to 14 AWG 120 in-lbs (13.56 Nm) 3 Large ground lug 2/0 to 14 AWG 120 in-lbs (13.56 Nm) 4 Neutral bus bar 4-6 AWG 8 AWG 10-14 AWG 35 in-lbs (3.95 Nm) 25 in-lbs (2.82 Nm) 20 in-lbs (2.
Electrical Connections Battery Installation WARNING Explosion. Batteries emit explosive gases while charging. Keep fire and spark away. Wear protective gear when working with batteries. Failure to do so could result in death or serious injury. (000137a) B A + – WARNING Risk of burns. Batteries contain sulfuric acid and can cause severe chemical burns. Wear protective gear when working with batteries. Failure to do so could result in death or serious injury. (000138a) WARNING Explosion.
Control Panel Startup / Testing Section 7: Control Panel Startup / Testing Control Panel Interface The control panel interface is located under the enclosure lid. Verify both left and right side locks are unlocked before attempting to lift enclosure lid. Open lid as directed in Opening the Lid. Using the AUTO/OFF/MANUAL Buttons Button Description of Operation AUTO Activates fully automatic system operation.
Control Panel Startup / Testing Display Reads Language English Troubleshooting + Use arrow keys to scroll to desired language. Press ENTER to select. Language can be changed later using the EDIT menu. 002227 - Enable Wi-Fi? Yes + Use arrow keys to either enable or disable Wi-Fi. If YES, see Wi-Fi manual. If NO, continue. 004498 Activate me (ENT) or ESC to run in manual Press ENTER to begin activation process.
Control Panel Startup / Testing Display Reads Troubleshooting Select Hour (0-23) - 6 + Activation is complete when this screen is displayed. Follow controller prompts to complete installation. 002231 Cold Smart Start The Cold Smart Start feature is factory-enabled, and can be disabled in the EDIT menu. Generator will monitor ambient temperature and adjust its warm-up delay accordingly when Cold Smart Start is enabled.
Control Panel Startup / Testing Interconnect System Self Test Feature This controller goes through a system self test at startup, which checks for utility voltage on DC circuits. This test prevents damage if installer incorrectly connected AC utility power sense wires into the DC terminal block. The controller will display a warning message and lock out the generator if utility voltage is detected at the DC terminal block, preventing damage to the controller.
Installation Guidelines for 60 Hz Air-Cooled Generators YES or NO Æ ENTER - 14 + * Select Hour (0-23) Å Cold Smart Start? Fuel Selection + NG or LP - No + Yes or No - Setup Wi-Fi? ENTER + English + Espanol + Francais + Portuguese + ...... - Language Note: If language was previously programmed this goes directly to “Select Hour” Use UP and DOWN arrows. to select YES or NO. Press ENTER.
38 ENTER SUB MENUS DATE/TIME * * Re-try using a higher quality USB drive. File names on the USB cannot have more than 8 characters. Possible Message(s): Corrupted File Invalid File File Not Found Unsupported Device* Switched to OFF Hours of Protection 0 (H) ENTER SETUP WIFI SYSTEM - 0 + Select Minute (0-59) ENTER ESC * ENTER ENTER * USB: X.XX Current: V X.XX * Install Wizard Set Exercise...
Control Panel Startup / Testing Checking Manual Transfer Switch Operation DANGER Electrocution. High voltage is present at transfer switch and terminals. Contact with live terminals will result in death or serious injury. (000129) See Manual Transfer Operation section of owner’s manual for procedures. Electrical Checks DANGER Electrocution. High voltage is present at transfer switch and terminals. Contact with live terminals will result in death or serious injury.
Control Panel Startup / Testing 9. Verify fuel pressure while running. Record running fuel pressure:________ 10. Set generator MLCB (generator disconnect) to ON (CLOSED). Loads are now powered by standby generator. 11. Turn on circuit breakers/electrical loads to be supplied by generator one by one. 12. Connect a calibrated AC voltmeter and a frequency meter across terminal lugs E1 and E2. Voltage should be approximately 240 volts and frequency should be approximately 60 Hz.
Control Panel Startup / Testing 4. Generator will start and run. Allow generator to run and warm up for a few minutes. 5. Set generator MLCB (generator disconnect) to ON (CLOSED). 6. Set utility MLCB to ON (CLOSED). The system now operates in automatic mode.
Control Panel Startup / Testing This page intentionally left blank.
Troubleshooting Section 8: Troubleshooting Generator Troubleshooting Problem Engine will not crank Cause Correction Blown fuse. Correct short circuit condition by replacing 7.5A fuse in generator control panel. Contact an IASD if fuse continues to blow. Loose, corroded, or faulty battery cables. Faulty starter contact. Tighten, clean, or replace as necessary.* Faulty starter motor. Discharged battery. Charge or replace battery. No fuel. Replenish fuel / turn on fuel shutoff valve.
Troubleshooting Problem Cause Correction Generator MLCB (generator disconnect) is OFF (OPEN). Set generator MLCB (generator disconnect) to ON (CLOSED). Faulty transfer switch coil. No transfer to Faulty transfer relay. standby after utility Transfer relay circuit open. source failure Faulty control logic board. Unit consumes large amounts of oil Contact an IASD for assistance Engine may be warming up. See Cold Smart Start. Check controller screen to verify status. Excessive engine oil.
Quick Reference Guide Section 9: Quick Reference Guide System Diagnosis To clear an active alarm, press ENTER button twice and then press AUTO. If alarm reoccurs, contact an IASD. Active Alarm NONE LED Problem FLASHING Unit running in AUTO but GREEN no power in house. Action Check generator MLCB (generator disconnect). Solution Check generator MLCB (generator disconnect). If it is ON, contact an IASD. HIGH TEMPERATURE RED Unit shuts down during operation.
Quick Reference Guide Active Alarm LED Problem OVERVOLTAGE RED Unit will not start in AUTO with utility loss. AUXILIARY SHUTDOWN RED Unit will not start. Action Solution Check LED’s / Screen Contact an IASD. for alarms. Check auxiliary shutdown switch(es). Set auxiliary shutdown switch(es) to CLOSED (I). LOW BATTERY YELLOW Yellow LED illuminated in any state. Clear alarm. Using control panel, check battery by navigating to BATTERY MENU option from MAIN MENU.
Accessories Section 10: Accessories Performance enhancing accessories are available for air-cooled generators. Accessory Cold Weather Accessories*— • Battery Pad Warmer • Oil Warmer • Breather Warmer Description • Recommended in areas where temperatures fall below 0 °F (-18 °C). (Not necessary for use with AGM-style batteries) • Recommended in areas where temperatures fall below 0 °F (-18 °C). • Recommended in areas where heavy icing occurs.
Accessories This page intentionally left blank.
Diagrams Section 11: Diagrams Installation Drawing (A0000973347 rev A—1 of 2) MOUNTING TO CONCRETE PAD 768 [30.2] 679 [26.8] HOLE LOCATIONS FOR OPTIONAL MOUNTING TO A CONCRETE PAD 521 [20.5] 16 [5/8] DIA. CLEARANCE HOLE (3) PLACES, 10 [3/8] DIA. MASONRY ANCHOR BOLTS RECOMMENDED 197 [7.7] 393 [15.5] 68 [2.7] 849 [33.4] FRONT OF UNIT 267 [10.5] 356 [14.
Diagrams Installation Drawing (A0000973347 rev A—2 of 2) AIR INTAKE 457 [18.0] MINIMUM OPEN AREA 914 [36.0] MINIMUM OPEN AREA AIR INTAKE AIR OUTLET 914 [36.0] MINIMUM OPEN AREA TOP VIEW 914 [36.0] MINIMUM OPEN AREA "DO NOT LIFT BY ROOF" LIFTING HOLES 4 CORNERS: 30 [ 1.2] - MUST BE LIFTED WITH STEEL RODS - RECOMMENDED LIFTING ROD SIZE: 25 [ RIGHT VIEW INTAKE PANEL REMOVED 1.0] 1218 [48.0] RIGHT SIDE VIEW 1232 [48.5] 127 [5.
® Part No. A0000973297 Rev. A 10/09/2020 ©2020 Generac Power Systems, Inc. All rights reserved. Specifications are subject to change without notice. No reproduction allowed in any form without prior written consent from Generac Power Systems, Inc. Generac Power Systems, Inc. S45 W29290 Hwy. 59 Waukesha, WI 53189 1-888-GENERAC (1-888-436-3722) www.generac.