LINE DIAGRAMS PWR CELL - A0000521683

Protected Loads / 100 A Service Sum Rule
- 1 PWRcell Inverter - 1 CT Kit (included)
- 3 PV Links (max 6)
- 1 PWRcell Battery
This design shows a PWRcell system with a Protected
Loads panel. This design uses the sum rule method for the load
side connection of an optional standby system. This design is
suitible for most residential 100 A 120 V / 240 V services.
Reference Code: DSLD00001-02
Page 04 of 19
NOTE: For load sizing,
max continuous current
is 32 A.
Generac Power Systems, Inc.• S45 W29290 Hwy. 59 • Waukesha, WI 53189© 2022 Generac Power System, Inc. All rights reservedPart No. A0000521683 | Rev. H | 18 JAN 2022
FOR REFERENCE ONLY; NOT FOR CONSTRUCTION.
*Installer responsible for code compliance.
*Refer to product documentation for additional installa-
tion details and requirements.
*Install SnapRS in PV array for module-level PVRSS requ-
-irements, one SnapRS per PV module.
CAT5
Comms Wiring
Control Wiring
DC Wiring (excluding REbus)
AC Wiring
Powered by REbus
TM
(DC Nanogrid)
Generac
PowerCore
30 A
30 A
30 A
30 A
Power Conversion
PWRcell
TM
Inverter
Router
50 A
Ethernet
AC Grid
Main Service
Panel
Protected Loads Panel
M
100 A
40 A 60 A
Loads Panel
CTs
Storage
PWRcell Battery
PV Array
PV Optimization
PV Link
TM
Substring Optimizer