Section 4: Installing PWRcell Inverter
Mounting the Inverter
(000641)
WARNING
Equipment damage. Mount inverter to a strong, stable surface.
Never mount to drywall, plaster, or other non-structural wall
treatments. Failure to mount inverter to a strong, stable surface
could result in equipment or property damage.
1. Verify mounting location adheres to the following
requirements:
Inverter must be mounted upright on a vertical wall.
Mounting surface must be a strong, stable surface.
Never mount to drywall, plaster or non-structural
building finishes.
Fasteners must engage with at least two studs or
other structural members.
Never obstruct intake or exhaust vents.
Never allow water to enter intake or exhaust vents.
See Figure 4-1. Observe all mounting clearances.
009989
A
F
B
G
H
I
C
D
E
K
L
J
Figure 4-1. Mounting Clearances
A 4 in (101.6 mm) G 24.5 in (622.3 mm)
B 19.25 in (489 mm) H 8 in (203.2 mm)
C 8 in (203.2 mm) I 28.5 in (723.9 mm)
D 20 in (508 mm) J 28 in (711.2 mm)
E 8.5 in (215.9 mm) K 36 in (914.4)
F 8 in (203.2 mm) L Floor
2. Verify fasteners are suitable for the mounting
surface and can adequately secure the inverter to
the wall. See Specifications for unit weight.
3. See Figure 4-2. Secure bracket (A) to mounting
surface. Fasteners must engage at least two studs
or other structural members.
NOTE: Mounting slots (B) accommodate dif
ferent stud
spacings.
A
B
009990
Figure 4-2. Installing Mounting Bracket
4. See Figure 4-3. Insert bracket tabs (C) into
inverter body slot (D).
C
D
009991
Figure 4-3. Mounting Inverter onto Bracket
5. See Figure 4-4. Secure inverter to wall with two
fasteners through mounting holes (E).
E
009992
Figure 4-4. Mounting Holes