Install Manual
Installing PWRcell Inverter
Installation Manual for Generac PWRcell Inverter 11
Section 4: Installing PWRcell Inverter
Mounting the Inverter
(000641)
WARNING
Equipment damage. Mount inverter to a strong, stable surface.
Never mount to drywall, plaster, or other non-structural wall
treatments. Failure to mount inverter to a strong, stable surface
could result in equipment or property damage.
1. Verify mounting location adheres to the following
requirements:
• Inverter must be mounted upright on a vertical wall.
• Mounting surface must be a strong, stable surface.
Never mount to drywall, plaster or non-structural
building finishes.
• Fasteners must engage with at least two studs or
other structural members.
• Never obstruct intake or exhaust vents.
• Never allow water to enter intake or exhaust vents.
• See Figure 4-1. Observe all mounting clearances.
009989
A
F
B
G
H
I
C
D
E
K
L
J
Figure 4-1. Mounting Clearances
A 4 in (101.6 mm) G 24.5 in (622.3 mm)
B 19.25 in (489 mm) H 8 in (203.2 mm)
C 8 in (203.2 mm) I 28.5 in (723.9 mm)
D 20 in (508 mm) J 28 in (711.2 mm)
E 8.5 in (215.9 mm) K 36 in (914.4)
F 8 in (203.2 mm) L Floor
2. Verify fasteners are suitable for the mounting
surface and can adequately secure the inverter to
the wall. See Specifications for unit weight.
3. See Figure 4-2. Secure bracket (A) to mounting
surface. Fasteners must engage at least two studs
or other structural members.
NOTE: Mounting slots (B) accommodate dif
ferent stud
spacings.
A
B
009990
Figure 4-2. Installing Mounting Bracket
4. See Figure 4-3. Insert bracket tabs (C) into
inverter body slot (D).
C
D
009991
Figure 4-3. Mounting Inverter onto Bracket
5. See Figure 4-4. Secure inverter to wall with two
fasteners through mounting holes (E).
E
009992
Figure 4-4. Mounting Holes