Datasheet
PWRcell Battery Foot Bracket Kit 1
PWRcell
®
Battery
Foot Bracket Kit
Requirements for Mounting Foot and
Wall Mount Brackets
The installation of this kit is required where battery instal-
lation is outdoors, or elevated greater than 1 3/4 in above
a floor.
Fastener Requirements
NOTE: The details below are minimum guidance. Con-
sult local building codes and a licensed contractor to
ensure the use of appropriate fasteners.
• Minimum 4 structural fasteners required for wall
bracket, corrosion protected steel, diameter 1/4 in.
• Minimum 4 structural fasteners required for foot
bracket. Use corrosion protected steel, diameter
1/4 in.
• Fastener head clearance 5/8 in tall, 7/8 in diameter.
• Use a flat washer between the fastener head and
wall bracket if fastener is not a flanged head.
• All fasteners must be field supplied.
• Installer must ensure that fasteners selected are
appropriately rated for this application.
Fastening Requirements
•
All fasteners must engage 1 1/2 in (3.8 cm) with a
structural member.
• If mounting into stud framing use a stud finder to
locate the center of the stud.
• If mounting into stud framing, the bracket must be
fastened to a minimum of two separate structural
members.
• If mounting to a foundation or masonry, make sure
fasteners are clear of any mortar joints.
• If stud is greater than 16 in on center, a cross brace
must be used.
• If mounting on vinyl siding, unistruts must be used.
• Brackets must be level.
• Each horizontal brace requires a minimum of two
fasteners.
Installing Foot Bracket
NOTE: A template is included on the inside of the PWR-
cell Battery packaging and will help locate the holes for
both wall and foot brackets.
Mount foot bracket to wall with the following procedure:
1. See Figure 1. Install the foot bracket bottom edge
to a minimum height of 3 in and a maximum height
of 6 in to keep the Battery Disconnect Switch at a
maximum height of 79 in above grade.
a. If greater height is desired, installation of an
additional DC disconnect listed 30 A 600 V will
be required for the battery to meet NEC
404.8(A).
Figure 1. Foot Bracket Install Height
2. See Figure 2. Locate structural members to mount
foot bracket (A). If structural members are greater
than 16 in apart, install cross brace to ensure
mounting to a solid structure.
3. See Figure 2. Install foot bracket (A) using lower
holes with fasteners and washers (B) making sure
bracket remains plumb and level.
NOTE: Do not install the top fasteners at this stage. This
will inhibit installation of the stands.
Figure 2. Install Foot Bracket
Grade
3 in MIN
79 in Max
013072
B
011153
A