Product Specifications
1 of 2
®
FEATURES
Generac's Smart Power Management System is designed to optimize the performance of a standby generator or PWRcell™ energy storage system (ESS). The system
can consist of up to eight individual Smart Management Modules (SMM). Unlike other load management systems that depend on another control device, the SMM is
self-aware and operates autonomously.
Frequency is the true measure of system performance, and does not need to factor in increased ambient temperatures, elevation changes, or generator fuel type. The
SMM monitors the frequency (Hz) of the power being produced by Generac’s standby generators or PWRcell ESS. If frequency falls below a certain threshold of a
correctly sized system, the SMM will automatically shed the managed loads to allow the system to recover.
The SMM can be set to a load priority between 1-8, or be set in a lock-out only mode for loads that do not need to run in an outage. This reduces the minimum size of
system required for a more cost-effective solution*.
* It is recommended to size the generator or PWRcell ESS with appropriate excess capacity to allow starting of the largest managed loads (i.e. loads with highest starting
currents). Each managed load of the SACM and SMM must be assigned a unique priority setting, so no two managed loads attempt to start simultaneously. See owner’s
manual for more information.
SMM SPECIFICATIONS
Power supply source .................................................................................................................................................................................. 240 VAC (from Line input)
Contact voltages.............................................................................................................................................................................................................220/240 VAC
Contactor coil voltage............................................................................................................................................................................................................ 240 VAC
Coil VA inrush ...............................................................................................................................................................................................................................300
Coil VA sealed.................................................................................................................................................................................................................................35
Poles.................................................................................................................................................................................................................................................2
Resistive amps ..............................................................................................................................................................................................................................100
F/L inductive amps ..........................................................................................................................................................................................................................90
Locked rotor amps.........................................................................................................................................................................................................................540
NEMA............................................................................................................................................................................................................................................. 3R
Enclosure rating ........................................................................................................................................................................................................................ UL 50
Frequency selectability ...................................................................................................................................................................................................50 Hz / 60 Hz
Wire gauge range box lugs..............................................................................................................................................................................................1/0 to 8 AWG
Wire material.................................................................................................................................................................................................................................. Cu
Coil pick up voltage......................................................................................................................................................................................................................80%
Coil drop out voltage ....................................................................................................................................................................................................................20%
Maximum contact voltage ....................................................................................................................................................................................................... 600VAC
Ambient temperature maximum .................................................................................................................................................................................... 149 °F (65 °C)
Coil terminals.........................................................................................................................................................................................................................18 AWG
Model: G007006-0
UPC: 696471077520
Smart Management
Module (SMM)
GENERAC
®
LOAD MANAGEMENT
100 Amp Smart Management Module (SMM)
Smart Management
Module (SMM)