Owner’s Manual for Mobile Light Tower 47
Troubleshooting
Troubleshooting Controller Fault Indicators
See Figure 5-1. When a fault occurs, the engine shuts off and an LED indicator illuminates on the controller.
Figure 5-1. Fault Indicator Button
IMPORTANT NOTE: To clear controller faults, press and hold the Fault Indicator button (Figure 5-1) for three sec-
onds.
Illuminated
LED
Indicates Fault Resolution
A Low engine oil pressure or
high engine coolant temperature
See General Troubleshooting —low oil pressure & high engine
coolant temperature.
A+C Engine overspeed or
engine underspeed
1. Check connection on W terminal of DC Charge Alternator—WH/
VI to pin-9 on the Power Zone controller.
2. Inspect function of DC charge alternator.
3. Inspect tension of DC charge alternator drive belt.
4. Contact Generac Mobile.
C Fail to crank
(AUTO mode only)
See General Troubleshooting —fail to crank
B+C Loss of speed
1. Check connection on W terminal of DC Charge Alternator—WH/
VI to pin-9 on the Power Zone controller.
2. Inspect function of DC charge alternator.
3. Inspect tension of DC charge alternator drive belt.
4. Contact Generac Mobile.