Installation Instructions

4
2.1 INTRODUCTION TO INSTALLATION
This equipment has been wired and tested at the factory. Installing
the switch includes the following procedures:
Mounting the enclosure.
Connecting power source and load leads.
Connecting the generator sensing and transfer relay circuits.
Connecting any auxiliary contact (if needed)
Connect Overload Prevention Control Board loads (as required)
• Testing functions.
2.2 MOUNTING
Mounting dimensions for the transfer switch enclosure are in this
manual. Enclosures are typically wall-mounted. See “Installation
Diagram”.
Handle transfer switches carefully when install-
ing. Do not drop the switch. Protect the switch
against impact at all times, and against con-
struction grit and metal chips. Never install a
transfer switch that has been damaged.
This transfer switch is mounted in a UL type 3R enclosure. It can
be mounted outside or inside and should be based on the layout
of installation, convenience and proximity to the utility supply and
load center.
Install the transfer switch as close as possible to the electrical
loads that are to be connected to it. Mount the switch vertically to
a rigid supporting structure. To prevent switch distortion, level all
mounting points. If necessary, use washers behind mounting holes
to level the unit.
2.3 CONNECTING POWER SOURCE AND
LOAD LINES
Make sure to turn OFF both the UTILITY
(NORMAL) and GENERATOR ( STANDBY)
power supplies before trying to connect power
source and load lines to the transfer switch.
Supply voltages are extremely high and dan-
gerous. Contact with such high voltage power
supply lines causes extremely hazardous, pos-
sibly lethal, electrical shock.
Wiring diagrams and electrical schematics are provided in this
manual.
NOTE:
All installations must comply with national, state and local
codes. It is the responsibility of the installer to perform an
installation that will pass the final electrical inspection.
The utility supply connection is made at the UTILITY SERVICE DIS-
CONNECT circuit breaker terminals. The generator and customer
load connections are made at the transfer switch mechanism,
inside the switch enclosure.
Conductor sizes must be adequate to handle the maximum cur-
rent to which they will be subjected, based on the 75°C column of
tables, charts, etc. used to size conductors. The installation must
comply fully with all applicable codes, standards and regulations.
All power cables must enter the enclosure through the knock-
outs provided. If not using the knockouts, conduit entry into the
enclosure must be at or below knockouts to maintain the Type 3R
rating. Conduits should be arranged to provide separation between
the Utility and Generator supply conductors inside the enclosure.
Before connecting wiring cables to terminals, remove any surface
oxides from the cable ends with a wire brush. If not using the
knockouts, entry must be at or below knockouts. If ALUMINUM
conductors are used, apply corrosion inhibitor to conductors.
Tighten terminal lugs to the torque values as noted on Utility
Service Disconnect Circuit Breaker, and on the decal located on
the inside of the door. After tightening terminal lugs, carefully wipe
away any excess corrosion inhibitor.
Use a torque wrench to tighten the conductors,
being sure not to overtighten, or damage to
the switch base could occur. If not tightened
enough, a loose connection would result,
causing excess heat which could damage the
switch base.
Connect power source load conductors to clearly marked transfer
mechanism terminal lugs as follows:
1. Connect UTILITY (NORMAL) power source cables to UTILITY
SERVICE DISCONNECT circuit breaker.
2. Connect the GENERATOR (STANDBY) source power cables to
transfer switch terminals E1, E2.
3. Connect customer LOAD leads to switch terminals T1, T2.
Conductors must be properly supported, of approved insulative
qualities, protected by approved conduit, and of the correct wire
gauge size in accordance with applicable codes.
Be sure to maintain proper electrical clearance between live metal
parts and grounded metal. Allow at least 1/2 inch for 100-400
amp circuits.
2.4 CONNECTING START CIRCUIT WIRES
Control system interconnections may consist of N1, N2, and T1,
and leads 0, 23 and 194. Reference instruction manual of specific
engine generator for wiring connection details. Recommended
wire gauge sizes for this wiring depends on the length of the wire,
as recommended in the following chart:
MAX WIRE LENGTH RECOMMENDED WIRE SIZE
460 feet (140m) No. 18 AWG.
461 to 730 feet (223m) No. 16 AWG.
731 to 1,160 feet (354m) No. 14 AWG.
1,161 to 1,850 feet (565m) No. 12 AWG.
Exceptions: If the insulation rating on all wiring is rated for 600V,
and the application meets code, it is acceptable to include genera-
tor control and power wiring in one conduit.
Installation