Functions
Dimensions
®
Generac Power Systems, Inc. • S45 W29290 HWY. 59, Waukesha, WI 53189 • generac.com
©2016 Generac Power Systems, Inc. All rights reserved. All specifications are subject to change without notice. Bulletin 10000007965 12/2/16
200 Amps, Single Phase Automatic Smart Transfer Switches
®
All timing and sensing functions originate in the generator controller
Utility voltage drop-out ......................................................................................................................................................................................................................<65%
Timer to generator start ....................................................................................................5 second factory set, adjustable between 2-1500 seconds by a qualified dealer*
Engine warm up delay ................................................................................................................................................................................................................. 5 seconds
Standby voltage sensor ..................................................................................................................................................................................................60% for 5 seconds
Utility voltage pickup .........................................................................................................................................................................................................................>80%
Re-transfer time delay ...............................................................................................................................................................................................................15 seconds
Engine cool-down timer ............................................................................................................................................................................................................60 seconds
Exerciser .................................................................................................................................................................. 5 minutes weekly, adjustable to bi-weekly or monthly
The transfer switch can be operated manually without power applied.
*When used in conjunction with units utilizing Evolution™ controls
Specifications
Model
RTSW200A3F
Height
(in./mm)
H1 48.0 / 1419.2
H2 42.9 / 1090
Width
(in./mm)
W1 22.5 / 571.5
W2 16.7 / 424
Depth (in./mm) 10.3 / 261.6
Weight (lbs./kilos) 85 / 38.6
Model RTSW200A3F
Amps 200
Voltage 120/240, 1ø
Load Transition Type
(Automatic)
Open Transition
Service Rated
Enclosure Type UL Type 3R
UL Rating UL
Withstand Rating
(Amps)
10,000
22,000*
Lug Range #1 - 300 MCM Al/CU 75 C
Integrated Load Center 8
Automatic Transfer Switches
*When used with 1" Siemens or Murray Breakers
H1
H2
W1
W2
Depth