Product Manual

General Information
6 Automatic Transfer Switch Owner’s Manual
Load Center Circuit Breakers
This switch is listed for use with the following one inch
breakers:
Siemens
Murray
Eaton*
Square D Homeline*
*Including GFCI, AFCI and tandem breakers up to 50 amps.
Eaton and Square D Homeline breakers limit rating to 10kA
SCCR.
NOTE: For branch circuits and feeders over 50 amps,
only listed Siemens or Murray circuit breakers shall be
used.
Service Disconnect Breaker and Terminal Ratings
Transfer Switch Data Decal
A data decal is permanently affixed to the transfer switch
enclosure. Use this transfer switch only with the specific
limits shown on the data decal and on other decals and
labels that may be affixed to the switch. This will prevent
damage to equipment and property.
When requesting information or ordering parts for this
equipment, make sure to include all information from the
data decal.
For future reference, record the Model and Serial
numbers in the space provided on the front cover of this
manual.
Transfer Switch Enclosure
The standard switch enclosure type is a NEMA 3R and
UL 3R outdoor rated enclosure.
Safe Use of Transfer Switch
Before installing, operating or servicing this equipment,
read the Safety Rules carefully. Comply strictly with all
Safety Rules to prevent accidents and/or damage to the
equipment. The manufacturer recommends that a copy
of the Safety Rules be posted near the transfer switch.
Also, be sure to read all instructions and information
found on tags, labels and decals affixed to the
equipment.
Two publications that outline the safe use of transfer
switches are the following:
NFPA 70; National Electrical Code
UL 1008: Standard for Safety—Automatic Transfer
Switches
UL67; Standard for Panelboards
NOTE: It is essential to use the latest version of any
standard to guarantee correct and current information.
Load Management Options
Load management systems are designed to work
together to prevent a generator from being overloaded by
large appliance loads. A Smart A/C Module (SACM) is
provided as standard equipment with this switch. An
optional Smart Management Module (SMM) is also
available.
Smart A/C Module (SACM)
Up to four air conditioner loads can be managed by the
SACM. The SACM manages the loads by “shedding” the
connected loads in the event of a drop in generator
frequency (overload). Loads to be “shed” are in 4 priority
levels on the module.
See Figure 2-2. Priorities A/C 1-4 (A) have connections
for an air conditioner. To control an air conditioner, no
additional equipment is required. Internal normally closed
relays interrupt the 24 VAC thermostat control signal to
disable the air conditioner load.
Four LEDs, located on the SACM (B), illuminate when a
load is connected and powered.
The SACM has a test button used to simulate an
overload condition. This button operates even when the
transfer signal is inactive.
Breaker Specification
Description Siemens MBK-200A Type EQ8695
2-pole, Single Phase
Voltage / Amp
Rating
240 VAC, 200A
(80% Current Rated)
Frequency 60 Hertz
Utility, Generator, and Subpanel
Connections
Tightening Torque
Utility
Connection
(N1 and N2)
#1 - 300MCM(Cu/Al)
75°C
250 in-lbs.
(28.2 Nm)
Generator / Load
Connection
(T1 and T2)
#6 - 250MCM (Cu/Al)
75°C
275 in-lbs.
(31.0 Nm)
Neutral #4 - 2/0 40–50 in-lbs.
(4.5–5.6 Nm)
Ground (2) or (3) 14 AWG 20 in-lbs. (2.3 Nm)
(2) 12-10 AWG 20 in-lbs. (2.3 Nm)
Control Wiring 11 in-lbs. (1.2 Nm)
(000100a)
WARNING
Consult Manual. Read and understand manual
completely before using product. Failure to
completely understand manual and product
could result in death or serious injury.