Install Instructions
General Filters
Incorporated
12 | P a g e
Figure 3.m.
: The standard steam unit comes with 6 feet (1.8m) of steam hose. Maximum total length of rubber steam hose is
3.65m (12 feet). The maximum total length of insulated copper tubing may be up to 6.1m (20 feet). The maximum combined allowed
length of steam hose and insulated copper tubing is 9.75m (32 feet). In all cases, minimize sharp bends and elbows. Use two 45°
elbows instead of one 90° elbows. Hose inner diameter
7
/
8
” (22 mm); Hose outer diameter 1 ¼” (30 mm). Additional steam hose is
available GFI #7513 / CGF #GF-20-2.
3.4.6. Remote Mount Blower
Refer to Section 10 for detailed Remote Mount Blower Installation Instructions.
20%
5%
20% 20%
5%
1,5 m (5 FT max.)
3 m (10 FT max.)
20%
0,9 m (3
FT max.)
1,5 m (5 FT max.)
1,5 m (5 FT max.)
YES
NO
P - TRAP
NOTE: HEIGHT OF TRAPSMUST BE GREATER
THAN THE DUCT STATIC PRESSURE
NOTES:
• SLOPEPIPING UPIN DIRECTION OF STEAM FLOW AT 20% OR GREATER, WHICH MEANS 65,5mm x 305mm (2 1/ 2” PER FOOT);
• SLOPEPIPING DOWN IN THE DIRECTION OFSTEAM FLOWAT 5% OR GREATER, WHICH MEANS 20mm x 305mm (3/4” PER FOOT);
• MAX. LENGTH OF RUBBER STEAM HOSE IS 3 m (10 FT).
• HEIGHT OF P-TRAPSMUSTBE GREATER THAN THE DUCT STATIC PRESSURE.
TYPICAL INSTALLATION
WHEN UNIT IS ABOVE
THE DISTRIBUTOR PIPE
GENTLEBEND
OBSTRUCTION
SUPPORTED STEAM HOSE
AND/ ORCOPPER PIPE
DRAINS
IF NO TRAP
WITH TRAP
DRAINS
IF NO SLOPE
NO SLOPE
NO SLOPE
KINKED
NO TRAP
UNDRAINED
ELBOW
UNDRAINED
ELBOW
NO DISTRIBUTION
PIPE DRAIN
SAG
NOTES:
• Slope piping up in direction of steam flow at 20% or greater, which means 1-1/2” per foot (65.5mm x 305mm).
• Slope piping down in the direction of steam flow at 5% or greater, which means ¾” per foot (20mm x 305mm).
• Max Length of rubber steam hose is 10 feet (3m).
• Height of p-traps must be greater than the duct static pressure.