Install Instructions

General Filters
Incorporated
16 | P a g e
4. START-UP
1. Before starting, check that there are no water leaks and that the electrical components are dry.
2. DO NOT connect power if the humidifier is damaged or even partially wet!
When installation is completed, flush the supply pipe for 10 minutes by piping water directly into the drain without sending it into the
humidifier. This will eliminate any scale or residue that may cause foam when boiling.
4.1 Start-Up Checklist
Before starting the humidifier, the following should be checked:
Water is connected, the line has been flushed, and external valves are open.
Min 1-1/2” ID drain is installed, but not connected to 90° elbow (supplied), run to an open drain, and has a trap under the unit.
Electricity is connected in accordance with instructions, local codes and data labels in the unit.
The 25 or 30A power fuses are installed and intact.
All AWG10 control wiring is done and tested.
The airflow switch is wired to open on air flow loss.
The Hi-limit humidistat is wired to open on humidity rise above set point.
Remove two screws securing control board. Unit wires should be checked to make sure they and all connectors are tight.
The steam hose(s) are run correctly with no sags or kinks and sloped properly according to the manual.
Condensate hose(s) are run correctly with no sags or kinks and sloped properly according to the manual.
4.2 The Elite Steam Humidifier Controller
The Elite Steam Humidifier Controller features a comprehensive information display that shows the
operation of the system at a glance:
1.
Display is % of nominal capacity
2.
Maintenance
3.
Display is amperage (default)
4.
Steam is being produced
5.
Cylinder filling
6.
Foaming
7.
Water presence inside the cylinder
8.
Cylinder draining
9.
LEDs indicate: power (yellow), operation (green) and alarms (red)
10.
Drain button for manual draining of cylinder and confirming parameter values
11.
ON/OFF button
12.
Reset button to reset alarms and access parameters
13.
Level of output: 33%, 66%, 100%
14.
Fan relay is activated (when fan icon on the control module is stationary, not flashing)
The Elite Steam Humidifier is now ready to operate.
4.3 Starting the Elite Steam Humidifier
Insure that the external power is turned on.
Push the top part of the ON/OFF button so that the I part is in (See #11 at right). The yellow
power LED will be lit. The Elite Steam Humidifier is now ready to operate.
When there is a call for humidity, the Elite Steam Humidifier will close its power relays and send
power to the electrodes in the plastic steam generator. The green Operation LED will light,
indicating that operation has begun.
4.4 Starting With A New Steam System or Replacement Steam Cylinder
When starting with a new cylinder, you should activate the cylinder cleaning function as follows:
1. Switch the Elite Steam Humidifier off.
2. Press and hold both buttons, “reset” and “drain”, and switch the Elite Steam Humidifier back on. When the wrench blinks
then release the two buttons.
3. Press and hold reset” until the display shows 04.
: DO NOT confirm any value higher than 04. If 05 or higher is displayed, press “resetuntil the display goes
back to the normal operating mode and restart from step 1.
4. Press “drain” (minimum 1 second): the cleaning starts and the display shows PC.
1
2
4
5
6
9
1012
13
14
11
3
7
8