10.7 Electrical Connections
The RMB fan is fitted with a power supply terminal block (Figure 10.c) with two terminals and a ground wire connector
on the housing.. The power wire should be 16 gauge or larger shielded cable with ground. Power wiring should be run
through the electrical knockout in the RMB and be secured with the supplied cable clamp.
The power will be supplied from the terminals “F” and “INT FAN” located on the back side of the humidifier control module.
The power wire must enter the humidifier through the bottom or back and then be secured inside the humidifier to prevent
tension on the wire or connections. To access the wire connection points on the back of the module, remove the steam
cylinder. Remove the protective caps on the connection points and use the two supplied spade connectors to make the
connections to the F and INT FAN terminals.
NOTE:
1. The power for the RMB unit is from the terminals on the BACK of the Control Module!
2. Electrical connections must be performed by qualified personnel in compliance with local codes.
Figure 10.e.
Figure 10.f.
Section through RMB flange and securing tab
SECURING TAB
BENT INTO POSITION
TO ATTACH TO
DRYWALL.
#8 SCREW
RUNS THROUGH FRONT
FLANGE AND INTO SLOT
IN SECURING TAB
FRONT OF RMB