Install Instructions

General Filters
Incorporated
7 | P a g e
3. INSTALLATION
3.1 Positioning
The Elite Steam Humidifier has been designed for wall mounting and, since it is an electrode steam humidifier, should be
placed close to the point where the steam will be used to minimize the steam hose length (and the amount of condensate).
Certain minimum clearances must be maintained around the unit for safety and maintenance.
(See Table 3.a. and Figure 3.a.)
DO NOT introduce steam into duct that has interior insulation.
3.2 Mounting / Unit Dimensions
3.2.1 Removing the Front Cover
The front cover is secured by four screws located at the four corners of the unit. Use a Phillips head screwdriver to remove
the four cover screws. Then simply pull the front cover away from the back part of the unit. Return it in reverse order.
Be careful not to over-tighten the screws.
(See Figure 3.b. and Table 3.b.)
Inch
Millimeters
A
6”
(150 mm)
B
6”
(150 mm)
C
6”
(150 mm)
D
6”
(150 mm)
E
24”
(600 mm)
max. 0.2°
Figure 3.a.
Inch
Millimeters
A
13.5“
341 mm
B
8.1“
204 mm
C
23.7“
600 mm
Pounds
Kilograms
Weight empty
18 lbs
8kg
Weight packaged
22 lbs
10kg
Weight installed with water
26 lbs
12kg
Unit Dimensions
Table 3.a.
Figure 3.b.