Operation And Maintenance Manual SSCB-15 SERIES CEILING MOUNTED ELECTRONIC AIR CLEANER IMPORTANT: PLEASE READ MANUAL BEFORE INSTALLING, OPERATING, CLEANING OR SERVICING UNIT
IMPORTANT: Please read entire instructions before installing the Electronic Air Cleaner. Installation and servicing of Electronic Air Cleaners can be hazardous. Only trained and qualified service personnel should install, repair, or service Electronic Air Cleaners.
approximately 7500 VDC. The collecting plates are alternately grounded and charged at 5000 VDC. The arrow on the cell indicates the direction of air flow which must point up towards the fan motor. Motor & Fan Blade The motor is 1/12 HP, 1050 RPM, 3 speed, controlled by a 3-position slide switch. The motor is thermally protected. The fan blade is aluminum, 18 inches (45.7 cm) with a 16˚ pitch. The Air Cleaner creates a circular air flow pattern which never allows air to rest at the ceiling. Fig.
give the unit the necessary stability when removing the cells or servicing the unit. The unit should be checked on a regular basis to determine the frequency of cleaning required in each location and a cleaning schedule established. Wiring Cleaning WARNING CAUTION Electrical shock can cause injury or death. Be certain main line disconnect switch is off before wiring. Make sure Air Cleaner switch is OFF before performing any maintenance or removing any components.
used as directed, DAX will not harm aluminum or steel. Any problem arising out of the use of another cleaning agent will void the warranty. Do not use detergents that are corrosive or abrasive or detergents containing chlorine or ammonia. 5. 5. SERVICE WARNING Electronic Air Cleaners use high voltage (low amperage). Only trained personnel should perform service. USE CAUTION! Electric shock can cause injury or death. CAUTION For most troubleshooting the cells should be removed from the Air Cleaner.
the input power to the unit is low. Voltage on power board may be too high when the installation area is too dry or too hot or the input power to the unit is high. By adjusting the HV Adj. potentiometer, the voltage can be set to optimum level. A high voltage meter capable of measuring 10,000 VDC is required. To test and adjust voltage level, perform the following procedure: 1. Turn the Air Cleaner OFF, with the cells in the unit. 2. Remove the power box cover panel. 3.
. Return power to Air Cleaner. 8. Test cell for proper operation. interlock switch. 4. Place a plastic handled screwdriver into the direction arrow slot. Do not apply excessive force. 5. There should be an initial snap when the plates are shorted, then no sound. If a hissing occurs, then there is a bad contact. Look along the top of the cell, with the short still in place. If there is a small arc between the cell top and copper contact, then that is the bad contact.
Fig. 5 — Electrical Schematic - 120 Volt Fig.
Table 1 — TROUBLESHOOTING GUIDE PROBLEM Unit does not function correctly. Power switch ON and performance indicator light and motor are OFF. Unit does not function correctly. Power switch is ON, motor is operating and performance indicator light is OFF. Unit does not function correctly. Power switch is ON, motor is not operating and performance indicator light is ON. PROBABLE CAUSE REMEDY Main breaker or fuse. Check breaker or fuse and reset or replace if necessary. Remote switch off.
Fig. 7 — Exploded View and Parts List # Description Part Number # Description Part Number 1 Fan Motor EACCM13-01 12a Power Switch (Black) EACCM13-12G 2 Fan Blade EACCM13-02 13 3-Position Slide Switch (Gray) EACCM13-13W 3 Copper Contact 13a 3-Position Slide Switch (Black) EACCM13-13G 4 Fibreboard (with 2 Copper Contacts) EACCM13-04 14 Power Board Fibreboard EACCM13-14 5 Intake Grill EACCM13-05 15 Power Board EACCM13-15 6 Cover Assembly (incl.
Dimensions Length 29.5 in 75.0 cm Width 27.0 in 68.6 cm Height 14.5 in 37.0 cm 95.0 lbs 43.0 kg Weight Input Voltage 120 V 60 Hz Power Consumption (max) 350 Watts Air Flow High 1300 CFM 2210 m3/hr Medium 1050 CFM 1785 m3/hr 750 CFM 1275 m3/hr Low Motor 1/12 HP Table 2 — Technical Data Fig.
ELECTRONIC AIR CLEANER LIMITED ONE YEAR WARRANTY Electronic Air Cleaners, if properly registered by the return of the attached warranty registration to General Filters, Inc., are warranted to the consumer against defects in materials and workmanship for a period of one year from the date of installation, so long as the product has been installed and operated in accordance with all appropriate manuals and wiring diagrams.