Resetting the MRT (The Max Run Timer is set automatically once the unit is
cycled between Limits. The Max Run Timer prevents the unit from running continuously
in the event of a problem. The MRT’s are set to the time required to run from one limit to
the other, plus 5 seconds (nominal). When the MRT is exceeded, the operator stops and
will not respond to any command until it is reset by pressing one of the calibration keys
or by cycling power to the unit.
CAUTION:
The MID-STOP feature must be turned off in order to properly set
the Max Run Timer.
CAL
RUN
AL
UN
LL
SCROLL
SET
CLEAR
O
CAL
RUN
R
OLL
OPEN
CLOSE
STOP
CAL
RUN
SCROLL
SCROLL
SET
CLEAR
ODC STB ON
Figure 16
NOTE Installation of Series II Monitored Photocells DOES NOT make the GCX unit legal for
residential use. The Genie® Company strictly prohibits any installation of a commercial
unit in any residentially zoned construction.
Monitored Reversing Devices
WARNING:
Photocell systems provide entrapment protection when mounted
near the doorway in such a way that the lower portion of an individuals leg will
break the photocell beam during normal walking through the doorway.
CAL
RUN
CAL
SET
CLEAR
SCROLL
OP N
LOS
CAL
RUN
SCROLL
C O
C A
CA
RUN
CROLL
TO RESET
1) Press CAL/RUN to enter calibration mode.
2) Press SCROLL (up or down) until display reads ”MAX RUN TMR > SET.” Fig. 15.
3) Press SET/CLEAR until display reads ”MAX RUN TMR > CLR.”
4) Press CAL/RUN to return to RUN mode.
5) Cycle the door between limits.
NOTE:
:
The Max Run Time must be reset each and every time the Travel Limits are adjusted.
ODC Safe-T-Beams® (OPTIONAL)
1) If operator is in RUN mode, press CAL/RUN to enter calibration
2) Press SCROLL (up or down) until display reads “ODC STB>ON”
“ODC STB>OFF” Figure 16
3) Press SET/CLEAR key to toggle between ON and OFF.
4) Press SCROLL (up or down)
to shift to a new function and lock setting.
5) Press CAL/RUN to return to run mode.
6.7
Current UL Approved Monitored Reversing Devices:
1) MillerEdge ME and MT series monitored edge sensors used in
combination with Timer-Close Module P/N OPABTCX.S.
2) MillerEdge ME and MT series monitored edge sensors used in
combination with OPAKMEIGX.S Interface Module. (Direct
connect through STB inputs).
5) Monitored Photocells P/N OPAKPEN4GX.S.
3) Residential Safe-T-Beam® Monitored Photocells from The Genie®
Company, model OSTB-BX (P/N 38176R.S).
4) Series II Safe-T-Beam® Monitored Photocells (P/N OPAKPE.S).
www.geniecompany.com 08-12
Counter Door Operator