User Guide

3
Stock # 6503V 1/3 HP 120/240 VAC CCW/CW
Stock # 6505V 1/2 HP 120/240 VAC CCW/CW
Stock # 6507V 3/4 HP 120/240 VAC CCW/CW
Stock # 6510V 1 HP 120/240 VAC CCW/CW
©2019, 2020, 2021 Regal Rexnord Corporation, All Rights Reserved. MCIM21055E • Form# G0134E
APPLICATIONS
Replacing
GE
®
*
model 2.0, Genteq
®
models 2.3 and Eon
®
motors
Applications
o Furnace, air handler and package units
o Fossil fuel, electric strip heat, A/C, heat pump and geothermal units
Install (1) Evergreen
®
VS user interface (Stock # 5K010V)
Install (1) Evergreen VS motor
o For proper replacement of model 2.0, Genteq ECM models 2.3 and Eon motors,
match the horsepower (HP) and voltage (VAC) ratings of the new Evergreen
VS motor to the motor being replaced. It is not necessary for the RPM or the
Amperage (FLA) to match.
All Evergreen VS motors are dual rotation (automatically configured at time of
installation) and dual voltage (established by the OEM harness)
Evergreen VS User Interface
Stock # 5K010V
Evergreen VS motor
GE Model 2.0 Genteq ECM
model 2.3 motor
Genteq ECM
Eon motor
REMOVAL AND INSTALLATION OF THE MOTOR
Remove the old motor
1. WARNING! Turn off the main line voltage disconnect to the HVAC system.
2. Unplug the 5-pin line voltage plug and the 16-pin communication plug from the ECM model 2.0, 2.3 or Eon motor.
3. Remove the old motor from the blower section. Leave the belly band mount connected to the blower section.
NOTE: If the original ECM motor is rated 3/4 or 1 horsepower (HP) and is installed in a 120 VAC application,
there should be a power factor correction choke wired in series with the line voltage 5-pin plug. This device
should be left in the system as connected by the HVAC OEM.
Install the new Evergreen VS motor
1. Install the new motor in the existing belly band mount so that the motor plugs are facing down
between the 4 and 8 o’clock position as installed in the HVAC system. Also adjust the motor so that the belly band does not block
any of the motor’s vents.
If the old motor was built with welded legs or other type of motor mount other than belly band, one of the belly band mounts
listed here should be a good match.
Stock # 5K002
48 Frame OEM mount
Stock # 5K003 / 5K004
48 Frame 10” / 11”
Stock # 5K005
48 Frame 13”
2. Go to the next page to find the instructions on how to connect the Evergreen VS user interface to the motor and HVAC system.
Operate the Evergreen VS motor for the first time in the HVAC system. With the first demand to operate the motor, the
motor will begin the rotation sensing process.
o Rotation Sensing - During the rotation sensing process, the motor will operate approximately 5-15 seconds in each
direction until it determines the proper direction of rotation. The motor will pause for a few seconds each time it stops
before restarting. The rotation sensing process is complete when the motor noticeably increases in speed and continues
to run in one direction for more than 30 seconds. From this point forward, the motor will always start in this direction. If
this is not the correct direction of operation, and the motor needs to be reversed after rotation sensing is complete, see
the bottom of page 10 (CHANGING ROTATION).