Product Brochure

Tandem Wiring Diagram
Relay Models
Models: 9123F, 9123TF, 9223F, 9223TF
Isolated Thermal with
Optional Accessory Contacts
Models: 9123H, 9123HF, 9223H, 9223HF
Limitations
Maximum of 12 alarms (9123, 9123T, 9123H, 9223, 9223T,
9223H) may be connected together
Do not exceed 125 ft. between each alarm
Do not exceed 1125 ft. between the rst and last alarm
Note: Gentex smoke alarms can not be interconnected
to alarms from other manufacturers
A maximum of six (6) alarms with a relay may be tandem
interconnected (9123F, 9123TF, 9123HF, 9223F, 9223TF,
9223HF)
Caution
RED/YELLOW wire to be capped when not in use
This wire is for tandem connection only
Do not connect to any other circuit
Relay Contacts Rated Load Resistive
1.0 AMP @ 24 VDC
0.6 AMP @ 125 VAC MAX
0.3 AMP @ 220 VAC MAX
BRN
Smoke
Alarm
Heat
Sensor
Access
Contacts
Alarm
Contacts
Tandem
Power
HF Only
BRN
GRAY
GRAY
YEL
ORN
BLU
VIO
VIO/BLK
RED/YEL
BLK
WHT
GRAYSupervision
Wires
Access
Contacts
Alarm
Contacts
Tandem
Power
GRAY
YEL
ORN
BLU
VIO
VIO/BLK
RED/YEL
BLK
WHT
Quick
Disconnect
Type Plug
1
2
3
1
2
3
1
2
3
120 Volts
60 Hz
Electrical Box
Electrical Box
Neutral
WHT
Tandem
RED /YEL
To additional
Gentex smoke alarms
Hot
BLK
Electrical Box
Smoke
Alarm
Smoke
Alarm
Smoke
Alarm