Product Brochure

CO1209 Series - Carbon Monoxide Alarm
Electrical Specications
Operating Voltage ............................................................ 120VAC, 60Hz
Operating Current .............................................................0.045 amps
Operating Current (Relay Options) ..............................0.070 amps
Operating Ambient Temp Range .................................40°F to 10F
Alarm Horn Rating ............................................................. meets or exceeds
85dBA at 10’
CO Sensing Cell ...................................................................Electrochemical Cell
“F” Auxiliary Relay .............................................................. 1 Form A and
1 Form C (0.6 amp)
Size ..........................................................................................Diameter: 6.25" OA
(5.75" at base)
Depth: 1.80
Secondary Power Source ................................................ Alkaline 9V battery
Duracell® MN 1604
CO1209 Series
Model Part Number Voltage (VAC)
Form A/C
Contacts
CO1209 918-0009-002 120 VAC
CO1209F 918-0010-002 120 VAC
Notes
Series available in round conguration only
Utilizing DUALINK®, if CO1209 is tandem interconnected with CO
alarms or combination smoke/CO alarms and CO devices go into
alarm, CO alarms and smoke alarm will sound CO warning.
Utilizing DUALINK®, if CO1209 alarm annunciates, all smoke
alarms, CO alarms or combination smoke/CO alarms tandem
interconnected will sound smoke alarm warning.
When both smoke and CO conditions are present, smoke condition
will have priority and alarm will sound smoke annunciation.
Units produce a temporal 4 audible alarm
Limitations
Maximum of 18 CO1209/CO1209F alarms may be connected
together
Do not exceed 125 ft. between each alarm
Do not exceed 1125 ft. between the rst and last alarm
Note: Gentex smoke alarms can not be interconnected to alarms
from other manufacturers
Caution
RED/YELLOW and BROWN/YELLOW wire to be capped when
not in use
This wire is for tandem connection only
Do not connect to any other circuit
Supervision
Wires
Access
Contacts
Alarm
Contacts
Tandem
Power
GRAY
GRAY
YEL
ORN
BLU
VIO
VIO/BLK
RED/YEL (LEGACY)
BRN/YEL (NEW)
BLK
WHT
Tandem Wiring Diagram Relay Model
Models: CO1209F