Product Brochure

Notes
Series available in round conguration only
Utilizing DUALINK®, if S1209 alarm annunciates, all smoke alarms, CO
alarms or combination smoke/CO alarms tandem interconnected
will sound smoke alarm warning.
Utilizing DUALINK®, if S1209 is tandem interconnected with CO
alarms or combination smoke/CO alarms and CO devices go into
alarm, CO alarms and smoke alarm will sound CO warning.
When both smoke and CO conditions are present, smoke condition
will have priority and alarm will sound smoke annunciation.
Units produce a temporal 3 audible alarm
S1209 Series - Photoelectric Smoke Alarm
Tandem Wiring Diagram
Electrical Specications
Operating Voltage ............................................................ 120VAC, 60Hz
Operating Current .............................................................0.045 amps
Operating Current (Relay Options) ..............................0.070 amps
Operating Ambient Temp Range .................................4F to 100°F
Alarm Horn Rating ............................................................. meets or exceeds
85dBA at 10
Nominal Sensitivity ........................................................... 2.5% obscuration
“F” Auxiliary Relay ..............................................................1 Form A and
1 Form C (0.6 amp)
Size ..........................................................................................Diameter: 6.25" OA
(5.75" at base)
Depth: 1.80
Secondary Power Source ................................................ Alkaline 9V battery
Duracell® MN 1604
S1209 Series
Model Part Number Voltage (VAC)
Form A/C
Contacts
S1209 917-0059-002 120 VAC
S1209F 917-0057-002 120 VAC
Relay Model
Models: S1209F
Caution
RED/YELLOW and BROWN/YELLOW wire to be capped when
not in use
This wire is for tandem connection only
Do not connect to any other circuit
Limitations
Maximum of 12 S1209/S1209F alarms may be connected together
Do not exceed 125 ft. between each alarm
Do not exceed 1125 ft. between the rst and last alarm
Note: Gentex smoke alarms can not be interconnected to alarms
from other manufacturers