Product Brochure
Notes
• Series available in round conguration only
• Utilizing DUALINK®, if S1209 alarm annunciates, all smoke alarms, CO
alarms or combination smoke/CO alarms tandem interconnected
will sound smoke alarm warning.
• Utilizing DUALINK®, if S1209 is tandem interconnected with CO
alarms or combination smoke/CO alarms and CO devices go into
alarm, CO alarms and smoke alarm will sound CO warning.
• When both smoke and CO conditions are present, smoke condition
will have priority and alarm will sound smoke annunciation.
• Units produce a temporal 3 audible alarm
S1209 Series - Photoelectric Smoke Alarm
Tandem Wiring Diagram
Electrical Specications
Operating Voltage ............................................................ 120VAC, 60Hz
Operating Current .............................................................0.045 amps
Operating Current (Relay Options) ..............................0.070 amps
Operating Ambient Temp Range .................................40°F to 100°F
Alarm Horn Rating ............................................................. meets or exceeds
85dBA at 10’
Nominal Sensitivity ........................................................... 2.5% obscuration
“F” Auxiliary Relay ..............................................................1 Form A and
1 Form C (0.6 amp)
Size ..........................................................................................Diameter: 6.25" OA
(5.75" at base)
Depth: 1.80”
Secondary Power Source ................................................ Alkaline 9V battery
Duracell® MN 1604
S1209 Series
Model Part Number Voltage (VAC)
Form A/C
Contacts
S1209 917-0059-002 120 VAC
S1209F 917-0057-002 120 VAC •
Relay Model
Models: S1209F
Caution
• RED/YELLOW and BROWN/YELLOW wire to be capped when
not in use
• This wire is for tandem connection only
• Do not connect to any other circuit
Limitations
• Maximum of 12 S1209/S1209F alarms may be connected together
• Do not exceed 125 ft. between each alarm
• Do not exceed 1125 ft. between the rst and last alarm
• Note: Gentex smoke alarms can not be interconnected to alarms
from other manufacturers