Operating Instructions

Appendix D RS-485 interface with Modbus protocol (RTU)
D.1 Prerequisites
!
Transmission parameter 1 stop bit, even parity
!
Transmission speed Factory setting: 9600
!
RS-485 interface protocol Modbus
D.2 "Read Holding Register" function (0x03)
Register name
Register-
number Type Value range
Factory
setting
Access
mode Unit
! Bus address 0000 unsigned word 1 … 255 1 R
! Baud rate 0001 unsigned word 0 9600
1 38400
2 57600
2 115200
57600 R [Bit/s]
! 0002
! Current flow
velocity
0003 unsigned word 0 … 15000 R [mm/s]
! Average flow
velocity
0004 unsigned word 0 … 15000 R [mm/s]
! Tilt anglel 0005 unsigned word 0 … 360 R [°]
! Internal filter
type
0006 unsigned word 0 IIR filter
1 Floating mean
1 R [1]
! Filter length 0007 unsigned word 1, 16 256 50 R [1]
! Flow direction 0008 unsigned word 0 Towards sensor
1 Away from sensor
R [1]
! Setting
Flow direction
0009 unsigned word 0 both
1 Towards sensor
2 Away from sensor
0 R [1]
! Measuring-
sensitivity
000A unsigned word 0 … 100 R [1]
! Signal intensity 000B unsigned word 0 … 2048 R [1]
! 000C
! Firmware version 000D unsigned word 000 … 999 R
! 000E
! Gain factor 000F unsigned word 0 1
1 2
2 5
3 10
4 20
5 50
6 100
7 200
R [1]
! 0010
30