Automatic Flushing
Depending on Temperature,
or Programmed
Hycleen Automation System − Application Flushing
If water stagnates over a longer period, bacteria can multiply in it until a dangerous
concentration is reached. If the entire volume in the drinking water distribution (cold and
hot water) is exchanged within three days, the bacteria are flushed out of the drinking
water installation and the bacteria concentration drops to a harmless level.
The Hycleen Automation System allows automatic flushing of cold and hot water supply
lines depending on the temperature or a specific time of day (timer).
Installations möglichkeiten Kombiantionen
Temperature controlled flushing
As soon as the threshold temperature at the temperature
sensor of a LegioTherm K flush valve is exceeded (cold wa-
ter) or undershot (hot water), the flush valve opens and clos-
es again after the pre-programmed time or when a certain
temperature is reached.
Temperature controlled flushing
T
Timed flushing
All LegioTherm K flush valves open as soon as the pre-set
time is reached and close after the defined flushing period.
The time interval between two flushing cycles can be set at
will, so that several flushing cycles per day are possible.
Each flushing process is logged.
Timed flushing