User Manual
Table Of Contents
- Welcome
- Important Notes for Maintaining Power Supply
- Elevator Control
- Optional Devices
- Installation Considerations
- Firmware and Software Compatibility
- Definition
- 1. GV-AS100 / 1010 Controller
- 1.1 Introduction
- 1.2 Installation
- 1.3 Programming Mode
- 1.4 Web-Based Configurations
- 1.5 GV-AS100 / 1010 Specifications
- 2. GV-AS110 / 1110 Controller
- 3. GV-AS120 Controller
- 4. GV-AS210 / 2110 / 2120 Controller
- 5. GV-AS410 / 4110 / 810 / 8110 Controller
- 6. GV-EV48 Controller
- 7. Installing on a Network
- 8. The Web Interface
- 9. Optional Devices
- 9.1 Optional GV-ASBox
- 9.1.1 Main Features
- 9.1.2 Packing List
- 9.1.3 GV-ASBox Board Layout
- 9.1.4 Installation
- 9.1.5 GV-ASBox Specifications
- 9.2 Optional GV-ASNet
- 9.3 Web Interface through Optional Devices
- 9.1 Optional GV-ASBox
- 10. Troubleshooting
- Appendix
GV-AS110 / 1110 Controller
51
2
2.3.2 Programming the GV-AS110 / 1110
The command codes used to program various functions on GV-AS110 / 1110 are listed
below. All command codes will start with an asterisk * to clear all previous commands and
end with a number sign # to send the command. After typing the command code, present
the Enroll Card or the Delete Card.
IMPORTANT: Once connecting to GV-AS110 / 1110, GV-ASManager will load its
parameters to GV-AS110 / 1110. That means some of settings you program here may be
overwritten by GV-ASManager later.
Function Command Code
Description
Set Password
*779_ _ _ _ _ _ _ _ #
4-8 digits
You can set a password to open the door using
this password. The Authentication Mode must
be set to Fixed Card/Common mode. Refer to
the Set Authentication Mode function below.
For example, to set the door’s password as
12345, press *77912345# on the keypad.
Lock Reset
Time
*578_ _ _ #
1-255 seconds
Sets a time that the door/gate will remain open
after which the door will automatically be
locked.
For example, to set the lock reset time to be
120 seconds, press *578120#
Held Open
Time
*468_ _ _ _ #
5-9999 seconds
Sets the time that a door/gate can be held open
before an alarm is generated. If the number of
seconds is less than 4 digits, add zeros in front
of the number to make it 4 digits.
For example, to set the held open time to be
180 seconds, enter *4680180#
Set Fire Action
(GV-AS110
only)
*732_#
UnchangedÎ0
Unlock DoorÎ1
Lock DoorÎ2
This function locks or unlocks the door/gate, or
maintains the current status when a fire
emergency occurs.
For example, to unlock door during a fire
emergency, press *7321#
Local Anti-
Passback
*527_#
0ÎDisable
1ÎEnable
Local Anti-passback prevents card sharing by
not allowing a card to go through an entry twice
before first exiting.
For example, to enable Local Anti-passback,
press *5271#