Once you have successfully completed the self-test and checked the
detector's sensor, you can then adjust the time setting and the lux value
(Fig. G) to suit your requirements. You can prevent unwanted triggering
of the device by using the lens mask as shown in Fig. H.
Device function based on Fig. G being set up as follows:
500 lux, 5 minutes.
Ifapersonenterstheeldofdetectionandthelevelofdaylight/ambient
light is higher than the detector's preset value (500 lux in the example),
theconnectedlightingwillremainswitchedo.Ifthelevelofdaylight/
ambient light falls below 500 lux and the detector senses a movement
within its eld of detection, the connected lighting will be switched
on and will remain on for the preset time specied on the detector
(5 minutes in the example). The time setting will restart each time a
movement is detected. If the full time period elapses without any further
movementbeingdetected,thedetectorwillautomaticallyswitchothe
connected lighting.
Recycling instructions
This device may not be disposed of with unsorted household
waste. Owners of old devices are required by law to dispose
of this device correctly. Contact your town council for further
information.
Troubleshooting - practical advice
Fault Cause Solution
Responds too late •Fieldofdetectionsetting
•Lensmaskisattached
•Head-onmovement
•Badlypositioned
•Turndetector
•Removemask
•Movedetector
Maximum range is not reached •Installedtoolow
•Dierencebetweentheambienttemperature
and the heat source is negligible
•Installthedetectorhigherup
Operates constantly or when not needed •Thereareheatsourcesandwarmmovements
such as sunlight, heaters, fans, etc. in the
detector'seldofdetection.
Device does not work •Nopowersupply
•Installationnotcompleted
•Checkfuse
•Checkinstallation,settings
•Ambientlightingistoobright
Technical data
Mains connection 230 V ~, 50 Hz
Field of detection 360°
Range approx. 7 m in diameter
Timesetting approx.5secondsto30minutes,innitelyvariable
Twilightswitch approx.10-2,000lux,innitelyvariable
Connected load load (L ) for lighting: µ
Incandescent lamp max. 2,000W
Halogen lamp max. 1,000W
Fluorescent lamp max. 900VA
Power consumption approx. 0.5 W
Operating temperature ange 0 °C to + 45 °C
Protection type IP 20
Protection class II
Test symbol TÜV
Recommended installation height approx. 2.5 m
Dimensions Ø 112 mm
μ=contactgap<1.2mm
Technical and design features may be subject to change without notice.