Owner's manual

4 Signet 2537 Flowmeter
Installation
Plastic sensor installation tips
Inspect the sensor O-rings for nicks and other damage that
may compromise the seal.
Lubricate O-rings with a non-petroleum based, viscous
lubricant (grease) compatible with the system.
Using an alternating/twisting motion,
lower the sensor into the  tting, making
sure the conduit ports on the yellow
housing are pointing in the direction
of  ow.
Engage one thread of the sensor cap
then turn the sensor until the alignment
tab is seated in the  tting notch.
sensor
cap
tab
notch
Lubricate
O-rings
Wiring
Electrical connections to this product should be made only by
quali ed personnel.
To access the wiring terminals:
Turn yellow cap ¼ turn counterclockwise to remove.
Remove the two retaining screws and remove the black
cover.
Route all cables through the conduit ports before connecting
them to the terminals.
Wiring terminals are rated for 16 to 22 AWG conductors.
The cable must be 7 to 10 mm in diameter (0.275 to
0.394 in.) to seal properly in the liquid tight connector.
The conduit ports have ½ inch NPT threads. After routing the
cables, seal the port with a liquid tight conduit connector
(3-9000.392-1) or with conduit.
For conduit installations:
Thread conduit with ½ in. NPT threads directly into the
conduit port.
For conduit with ISO threads, use the black thread adapter
included with the connector kit.
To comply with NEC requirements, do not use any metal
conduit in the installation.
2537 Paddlewheel Flowmeter
for ½ in. to 4 in. pipe
130 mm
(5.12 in.)
97 mm
(3.82 in.)
2537 Paddlewheel Flowmeter
for 5 to 8 in. pipe
171 mm
(6.73 in.)
97 mm
(3.82 in.)
Dimensions
S1
S2
Blk Red Shld
-
+
3-8900.621C
I/O Module 3-8900.401-X
1
2
3
4
5
6
7
8
9
10
11
12
13
14
+5VDC (Black)
Freq. Input (Red)
GND (Shield)
+5VDC (Black)
Freq. Input 2 (Red)
S L (Red)
GND (White/Shield)
+5VDC (Black)
S L (Red)
GND (White/Shield)
3
3
Analog Output 1
Analog Output 2
(if applicable)
(if applicable)
Frequency
Input
1
Frequency
Input 2
OR
S
3
L
Input
2
S
3
L
Input
1
+
-
+
-
S1
S2
Blk Red Shld
-
+
DATA
GND
V+
SHLD
Wiring: Digital (S
3
L) Output
The Digital (S
3
L) output is compatible with the 3-8900 Multi-Parameter Controller
and the 3-9900 Transmitter.
-
+
S1
S2
Blk Red Shld
-
-
+
+
-
+
-
+
-
+
-
+
T
T
P
t
WIRING DIAGRAM
BLK
RED
SHLD
Sensor
PW/OUT
+
Power Rating:
5 - 6.5VDC 0.03 AMP
3-2505.613A
T
P
t
T
P
t
T
P
t
S1
S2
Blk Red Shld
-
+
WIRING DIAGRAM
BLK
RED
SHLD
Sensor
PW/OUT
+
Power Rating:
24VDC 0.03 AMP
3-2505.611A
N/O
COM
N/C
Dry-Contact
Relay
Relay Rating:
5A @ 250VAC
5A @ 30VDC
Using the liquid-tight
connector
Using conduit
HAND-TIGHTEN THE THREADED NUT ONTO THE IN-
STALLATION FITTING. DO NOT USE TOOLS! DO NOT
USE THREAD SEALANT OR LUBRICANTS ON THE
FITTING THREADS OR THE SENSOR CAP.
Connection to
9900 Transmitter
Connection to
8900 Controller