Datasheet

EPIC
®
Hermetic Sealed DC and AC Contactor - 225+ Amp Power Switchin
g
RoHS Compliant, all date codes
Patent Pending
File E320908
All contact ratings and coil versions
may not be UL recognized.
Contact GIGAVAC
for a copy of the
applicable sections of the test report.
Chassis level UL508 sized power terminal
s
No need for specially
routed power cables, special bus bars, or special lugs.
Rugged EPIC
®
Seal rated to 175°C Reduced risk of fire or meltdown
in over current conditions. The same technology used for advanced
aeros
p
ace
p
ro
g
rams
.
Hermetically Seale
d
Designed to meet: UL1604 for Class I & II, Div 2
and Class III for use in hazardous locations, IP67 for temporary water
immersion for 30 min, SAE J1171 - external ignition protection, and
ISO8846 for
p
rotection a
g
ainst i
g
nition around flammable
g
asses
.
Optional High Efficiency Dual DC Coil
s
Very low 12 or 24 VDC
continuous coil power with no EMI emissions or cross-talk on your
system control power. Ideal for battery powered systems or where low
power is needed.
Built-in coil suppression for all DC coil
s
Saves you engineering
time and parts cost to add external coil suppression.
Stainless steel hardware and mounting insert
s
, for years of corrosion
free service
UL508 ambient compliant to 75°C but can operate continuously at 85°
C with a higher terminal temperature rise of 60°C. Can also operate up
to 125°C in special cases - contact GIGAVAC for details.
Not position sensitive
can be mounted in any position for ease of
installation
.
Electrical life rating is based on resistive load with 2
7
µH maximum inductance in circuit. Because your application may be
different, we suggest you test the contactor in your circuit to verify life is as required.
End of life is defined as when the dielectric, insulation resistance or contact resistance exceeds the specifications listed
.
If your application requires a higher current rating, you may want to consider the GIGAVAC 350 Amp GX14 EPIC
®
sealed
contacto
r
.
Make & Break Resistive Current
with 4/0 cable and 50°
terminal temp rise
Contact Voltages & Life Cycle Rating
s
DC or 50/60 Hz AC
24
V
48
V
72
V
120
V
350
V
750
V
225A -
(
75° C Ambient) 1/ 150,00
0
100,00
0
40,00
0
20,00
0
7,50
0
1,20
0
150A -
(
75° C Ambient
)
1/ 225,00
0
150,00
0
60,00
0
30,00
0
11,250 1,80
0
125A - (75° C Ambient) 1/ 270,000 180,000 72,000 36,000 13,500 2,160
100A -
(
75° C Ambient
)
1/ 337,50
0
225,00
0
90,00
0
45,00
0
16,87
5
2,70
0
75A -
(
75° C Ambient
)
1/ 450,00
0
300,00
0
120,00
0
60,00
0
22,50
0
3,60
0
50A - (75° C Ambient) 1/ 675,000 450,000 180,000 90,000 33,750 5,400
30A -
(
75° C Ambient
)
1/ 1,000,00
0
750,00
0
300,00
0
150,00
0
56,25
0
9,00
0
20A - (75° C Ambient) 1/ 1,000,000 1,000,000 450,000 225,000 84,375 13,500
275A -
(
50° C Ambient
)
2/ 127,50
0
85,00
0
34,00
0
17,00
0
6,37
5
1,02
0
Max Break A, 2 cycle
s
(75° C Ambient) 1/
2,750A 2,200A 1,650A 1,100A 990A 660A
Max Make, 10 cycle
s
(75° C Ambient) 1/
1,540A 1,210A 880A 660A 550A 385A
1/ Assumes UL508 ratings with 4/0 cables, UL508 max ambient temperature of 75°C as shown, and max. UL508 terminal
t
emperature rise of 50°C. For loads of 150A and below and the life cycle rating shown is longer than you need, you may
w
ant to consider the lesser priced GIGAVAC GX11 EPIC® sealed contactor. Smaller sized cables can be used at the
lower currents - see UL specifications for recommended cable sizes.
A
t 85°C ambient, contactor can also meet all of its 75°C specifications but the terminal temperature can rise can be up to
60°C, which is higher than the 50°C rise allowed by UL508 and can be higher than some cable insulation ratings.