User's Manual

Table Of Contents
Important Safety Information
Page 10 MDE-3883 TRIND Retrofit Kits C00011-005
10/00
PRELIMINARY
FCC 11/30
React Quickly to Fuel Spills, Fires or Vehicle Impact
Follow these steps in the event of a fuel spill, fire, or vehicle impact.
1 Use station EMERGENCY TOTAL ELECTRICAL SHUT-OFF immediately. Turn off all
system circuit breakers to the island.
2 Call emergency numbers for fires, vehicle impact or any significant spills.
3 Use safety tape, cones or barricades to block the work area. Do not go near fuel spill or
allow anyone else in the area.
4 Take precautions to avoid igniting fuel. Do not allow starting of
vehicles in the area and immediately stop use of open flames, smoking or power tools in the
area.
5 Provide emergency and first aid assistance.
6 Use approved and safe procedures to clean up all spills with a fuel or gasoline absorbent
material approved by your local regulatory agencies. (Dispose of fuel and hazardous absorbent
material promptly and according to the requirements of the fire department, local EPA, and
federal, state or local resources.)
The EMERGENCY STOP, ALL STOP, and PUMP STOP buttons at the cashiers
station WILL NOT shut off electrical power to the pump/dispenser.
This means that even if you activate these stops, fuel may continue to flow
uncontrolled.
You must used the TOTAL ELECTRICAL SHUT-OFF in the case of an emergency
and not only these cashier station stops.
WARNING
If any gasoline has been inhaled, seek emergency help immediately.
Inhaled gasoline may cause unconsciousness and burns to lips, mouth and lungs.
WARNING
Gasoline spilled on skin may cause burns.
Wash area thoroughly with clean water.
Seek medical advice immediately.
WARNING