Spec Sheet
Gillette Generators, Inc. •
••
• 2921 Thorne Dr. •Elkhart, IN • 46514 • Ph: 574-264-9639 • Fax: 574-262-1840 • Web: www.gillettegenerators.com • spc4-190104
1
PRIME MODEL
PR-800
60 HERTZ
All generator sets are USA prototype built and thoroughly tested.
Production models are USA factory built and 100% load tested.
UL1446, UL508, UL142, UL498
NFPA 110, 99, 70, 37
All generator sets meet NFPA-110 Level 1, when equipped with the
necessary accessories and installed per NFPA standards.
NEC 700, 701, 702, 708
NEMA ICS10, MG1, ICS6, AB1
ANSI C62.41, 27, 59, 32, 480, 40Q, 81U, 360-05
ASCE 7-05 & 7-10
All generator sets meet 180 MPH rating.
EPA 40CFR Part 60, 1048, 1065, 1068
RATINGS: All single phase gen-sets are dedicated 4 lead windings, rated at unity (1.0) power factor. All three phase gen-sets are 12 lead windings, rated at (.8) power
factor. 105°C “PRIME RATINGS” are strictly for gen-sets provide the prime source of electric power, where normal utility power is unavailable or unreliable. A 10%
overload is allowed for a total of 1 hour, within every 12 hours of operation of PRIME RATED systems. All gen-set power ratings are based on temperature rise measured
by resistance method as defined by MIL-STD 705C and IEEE STD 115, METHOD 6.4.4. All generators have class H (180°C) insulation system on both rotor and stator
windings. All factory tests and KW/KVA charts shown above are based on 105°C (prime) R/R winding temperature, within a maximum 40°C ambient condition.
Specifications & ratings are subject to change without prior notice.
LIQUID COOLED NAT. GAS ENGINE GENERATOR SET
GENERATOR RATINGS
NATURAL GAS FUEL
POWER LEAD
CONNECTIONS
GENERATOR MODEL
VOLTAGE
PH HZ
105°
°°
°C RISE PRIME RATING
L-N L-L KW/KVA AMP
PR-800-1-1
120 240 1 60 80/80 333 4 LEAD DEDICATED 1 PH.
PR-800-3-2
120 208 3 60 80/100 278 12 LEAD LOW WYE
PR-800-3-3
120 240 3 60 80/100 241 12 LEAD HIGH DELTA
PR-800-3-4
277 480 3 60 80/100 120 12 LEAD HIGH WYE
PR-800-3-5
127 220 3 60 80/100 263 12 LEAD LOW WYE
PR-800-3-16
346 600 3 60 80/100 96 4 LEAD DEDICATED 3 PH.
“OPEN” GEN-SET
There is no enclosure, so gen-set must be
placed within a weather protected area,
un-inhabited by humans or animals, with
proper ventilation. Silencer not supplied,
as installation requirements are not
known. However, this item is available as
optional equipment.
“LEVEL 2” HOUSED GEN-SET
Full aluminum weather protection and
superior sound attenuation for specific low
noise applications. Critical grade muffler
is standard.
Model
PRIME
105ºC RISE
HZ NATURAL GAS
PR
-
800
-
60 HERTZ
60 80