Spec Sheet
Gillette Generators, Inc. •
••
• 2921 Thorne Dr. •Elkhart, IN • 46514 • Ph: 574-264-9639 • Fax: 574-262-1840 • Web: www.gillettegenerators.com • spc4-190130
1
GENERATOR RATINGS
GENERATOR
MODEL
VOLTAGE
PH HZ
130°
°°
°C RISE STANDBY RATING 105°
°°
°C RISE PRIME RATING
L-N L-L KW/KVA AMP KW/KVA AMP
T4D-3000-3-2
120 208 3 60 300/375 1042 300/375 1042
T4D-3000-3-3
120 240 3 60 300/375 903 300/375 903
T4D-3000-3-4
277 480 3 60 300/375 451 300/375 451
T4D-3000-3-5
127 220 3 60 300/375 985 300/375 985
T4D-3000-3-16
346 600 3 60 300/375 361 300/375 361
RATINGS: All three phase gen-sets are 12 lead windings, rated at .8 power factor. 130° C “STANDBY RATINGS” are strictly for gen-sets that are used for back-up
emergency power to a failed normal utility power source. This standby rating allows varying loads, with no overload capability, for the entire duration of utility power
outage. 105° C “PRIME RATINGS” are strictly for gen-sets that provide the prime source of electric power, where normal utility power is unavailable or unreliable. A 10%
overload is allowed for a total of 1 hour, within every 12 hours of operation, on every PRIME RATED systems. All gen-set power ratings are based on temperature rise
measured by resistance method as defined by MIL-STD 705C and IEEE STD 115, METHOD 6.4.4. All generators have class H (180°C) insulation system on both rotor and
stator windings. All factory tests and KW/KVA charts shown above are based 130°C (standby), and 105°C (prime) R/R winding temperature, within a maximum 40°C
ambient condition. Generators operated at standby power ratings must not exceed the temperature rise limitation for class H insulation system, as specified in NEMA MG1-
22.40. Specifications & ratings are subject to change without prior notice.
LIQUID COOLED DIESEL ENGINE GENERATOR SET
60 HZ MODEL
T4D-3000
“OPEN” GEN-SET
There is no enclosure, so gen-set must be
placed within a weather protected area, un-
inhabited by humans or animals, with proper
ventilation. Silencer not supplied, as
installation requirements are not known.
However, this item is available as optional
equipment.
All generator sets are USA prototype built and thoroughly tested.
Production models are USA factory built and 100% load tested.
UL1446, UL508, UL142, UL498
NFPA 110, 99, 70, 37
All generator sets meet NFPA-110 Level 1, when equipped with the
necessary accessories and installed per NFPA standards.
NEC 700, 701, 702, 708
NEMA ICS10, MG1, ICS6, AB1
ANSI C62.41, 27, 59, 32, 480, 40Q, 81U, 360-05
ASCE 7-05 & 7-10
All generator sets meet 180 MPH rating.
EPA 40CFR Part 60, 89, 1039, 1048, 1054, 1065, 1068
“LEVEL 2” HOUSED GEN-SET
Full aluminum weather protection and superior
sound attenuation for specific low noise
applications. Critical grade muffler is standard.
Model
STANDBY
130ºC RISE
PRIME
105ºC RISE
HZ
T4D
-
30
00
-
60 HERTZ
60 300 300