9.2 Horizontal Telescopic Flue - A2043600
Refer to diagram 9.2 for kit contents.
9.3 REAR Flue
If a wall thickness is between 210mm min. to 420mm max.
then the ue can be used without extensions.
Temporarily secure the ue elbow, measure the distance
from the outside wall to the butt joint, see diagram 9.4. If
the measurement ‘Y’ exceeds 525mm, then the appropriate
length of extension pipe is required.
If the dimension is less than 315mm DO NOT cut the ue, it
can project to a maximum of 600mm, refer to diagram 9.5. If
this is not desirable then a Standard ue MUST be used and
cut to length.
9.4 SIDE Flue
Temporarily secure the ue elbow, measure the distance
from the outside wall to the butt joint, see diagram 9.6. If
the measurement ‘Y’ exceeds 525mm, then the appropriate
length of extension pipe is required.
If the dimension is less than 315mm DO NOT cut the ue, it
can project to a maximum of 600mm, refer to diagram 9.5. If
this is not desirable then a Standard ue MUST be used and
cut to length.
Diagram 9.4
14471
Diagram 9.5
12979