9.7 Standard Horizontal Flue - A2043400
Refer to diagram 9.11 for kit contents.
9.8 REAR Flue
Temporarily secure the ue elbow, measure the distance
from the outside wall to the butt joint, see diagram 9.13. If
the measurement ‘Y’ exceeds 665mm, then the appropriate
length of extension pipe is required. The minimum dimension
is 180mm to suit a 75mm min wall thickness. The ue can
project to a maximum of 600mm, refer to diagram 9.14.
9.9 SIDE Flue
Temporarily secure the ue elbow, measure the distance
from the outside wall to the butt joint, see diagram 9.15. If
the measurement ‘Y’ exceeds 665mm, then the appropriate
length of extension pipe is required. The minimum dimension
is 262.5 to suit a minimum wall thickness of 75mm. The ue
can project to a maximum of 600mm, refer to diagram 9.14.
9 Standard Flue - Length, Preparation and Installation
20
Diagram 9.13
14471
Diagram 9.14
12979
Diagram 9.15
14473