9 Twin Flue - Length, Preparation and Installation
9.16 Twin ue
The twin ue system is available as an option when the top
horizontal or vertical ue system is not appropriate.
The system can provide an independent horizontal air inlet
and ue outlet, horizontal air inlet and vertical ue outlet or
vertical air inlet and ue outlet via a concentric terminal.
The system is made up from accessories, see diagram 9.25.
NOTE: The air and ue outlets do not have to be equal
lengths. 2x45º bends can replace 1x90º bend if necessary.
The maximum permitted combined (air inlet + ue outlet) ue
length is 14,3 metres for Betacom 24C, 11,9 metres for
maximum ue length must be reduced by 1 metre, see
diagram 9.24.
NOTE: When using 90º bends any horizontal run should be
inclined by a minimum of 44mm/metre (2.5º) towards the
boiler to facilitate condense removal.
Alternatively use 45º bends to avoid horizontal runs in the ue
pipe.
9.17 Terminal Position
The clearances for a ue outlet are given in the "Flue Location
and Ventilation" section.
In addition the horizontal air inlet must not be closer than 300
mm from a ue outlet on the same wall or 1200mm from an
opposing ue outlet.
9.18 Installation Details
The parts available for a twin ue system installation are
shown in diagram 9.25.
Diagram 9.25