7 221564F
1 General Information
Diagram 1.2
For larger systems use an additional expansion vessel.
Ball valves are fitted in water and gas connections, plus a drain point on all water connections.
80 100
Lift Weight 72kg (158.7lb) 77kg (169.7lb)
Total Weight (packed) 76kg (167.5lb) 81kg (178.6lb)
Total Weight (installed) 94kg (207.2lb) 99kg (218.3lb)
Gas connection Rc
1
/
2
(
1
/
2
in BSPT)
Heating and return 22mm compression
Domestic hot water 15mm compression
Safety valve Preset 3bar (43.5lbf/in
2
)
Safety valve discharge 15mm copper
80 100
Water content (heat exch) 2.7 ltr (0.59 gall) 4 ltr (0.88 gall)
Water content (primary store) 13 ltr (2.86 gall) 12.4 ltr (2.7 gall)
Water content (domestic) 1.3 ltr (0.29 gall) 2 ltr (0.44 gall)
Expansion vessel capacity 7 litres (1.54 gallons)
Charge pressure 0.5bar (7.3lbf/in
2
)
Heating system 0.7bar (10.1lbf/in
2
)
minimum pressure
Domestic hot water flow rate
80 100
temp rise 30
0
C 11.4l/min (2.5gall/min) 13.3l/min (2.9gall/min)
35
0
C 9.8l/min (2.2gall/min) 11.4l/min (2.5gall/min)
Maximum flow temperature 65
0
C
Minimum working pressure 0.1bar
Maximum heating 130 litres
system water (28.6 gallons)
content using at 75
0
C
fitted expansion average system
vessel, pressurised temperature
at 1bar.
Electrical supply 230V~50Hz
Electrical rating 115W fused 3A
TABLE 2
6499
NOMINAL kW
80
27.5 27.5 8.0
HEAT Btu/h 93,830 93,830 27,266
INPUT kW
100
32.5 32.5 10.2
GROSS Btu/h 110,890 110,890 34,802
NOMINAL kW
80
24.5 24.5 6.8
HEAT Btu/h 83,600 83,600 23,200
OUTPUT kW
100
28.8 28.8 8.9
Btu/h 98,266 98,266 30,367
COND. kW
80
25.5 25.5 7.7
HEAT Btu/h 87,000 87,000 26,170
OUTPUT kW
100
30.5 30.5 9.8
Btu/h 104,066 104,066 33,438
BURNER
mbar
80
-4.5 -4.5 -0.5
MANIFOLD
wg
-1.8 -1.8 -0.2
SUCTION
PRESSURE
mbar
100
-4.8 -4.8 -0.5
HOT(APPROX)
wg -1.92 -1.92 -0.2
80
9.2-9.6 9.2-9.6 9.2-9.6
BURNER
9.0-9.4 9.0-9.4 9.0-9.4
%CO
2
100
9.2-9.6 9.2-9.6 9.2-9.6
9.0-9.4 9.0-9.4 9.0-9.4
m
3
/h
80
2.6 2.6 0.7
ft
3
/h 91.8 91.8 24.7
D.H.W Max. 8bar
working pressure (150lbf/in
2
)
IP classification IP40
Internal Fuse rating 1) Type 2AF
2) Type 2AF
3) Type 3AT
TABLE 1 C.H. Max D.H.W.Max MIN
CASING
DOOR ON
CASING
DOOR OFF
CASING
DOOR ON
CASING
DOOR OFF
m
3
/h
100
2.9 2.9 0.9
ft
3
/h 102.4 102.4 31.8
APPROX.
GAS RATE
SCHEMATIC LAYOUT OF BOILER