INSTALLATION
- 15 -
Where possible keep the existing boiler/circulating pump in
place when ushing the system
5.6.2 Flushing the system
Fill the system with cold water and check for leaks.
Open all drain cocks and drain the system.
Close drain cocks and add a suitable ushing agent (cleaner)
compatible with Aluminium at the correct strength for the
system conditions in accordance with the manufacturers
instructions.
Examples of suitable ushing agents/cleansers are:
Sentinel X300, X400
Fernox F3
• Circulate the ushing agent before the boiler is red up.
Run the boiler/system at normal operating temperature as
directed by the manufacturer of the ushing agent.
It is essential to drain and thoroughly ush the whole system
to remove the ushing agent and debris.
It may be necessary to use a power ushing machine to aid
the cleansing procedure in some circumstances.
Close the drain cocks and re ll with fresh water and a
suitable inhibitor.
Vent any air from the boiler and system.
5.6.3 Inhibiting the system
Add a suitable inhibitor or combined inhibitor/anti-freeze, if the
system is exposed to freezing conditions, to the heating system
in accordance with the DWTA code of practice and inhibitor
manufacturers guidelines.
Examples of suitable inhibitors are:
Sentinel X100
Fernox protector F1
Arti cially softened water must not be used to
ll the central heating system.
Sealing agents - The addition of sealing agents
to the system water is not permitted as this can
cause problems with deposits left in the heat
exchanger.