INSTALLATION
- 18 -
Diagram 5.5
11680
5.15 Pressure Gauge
A pressure gauge with a set pointer and covering at least 0 to 4
bar (0 to 60 lb/in2) shall be tted permanently to the system in a
position where it can be seen when lling the system.
5.16 Water Makeup
Provision should be made for replacing water loss from the sys-
tem using a make up bottle mounted in a position higher than
the top point of the system, connected through a non-return
valve to the return side of either the heating circuit or the hot
water cylinder.
Alternatively, provision for make up can be made using a lling
loop.
5.17 Filling a Sealed Water System
Provision for lling the system at low level must be made, see
diagram 5.5. There must be no permanent connection to the
mains water supply, even through a non-return valve.