10 Twin Flue - Length, Preparation and Installation
Diagram 10.30
10.15 Twin ue length
The twin ue system is available as an option when the top
horizontal or vertical ue system is not appropriate.
The system can provide an independent horizontal air inlet
and ue outlet, horizontal air inlet and vertical ue outlet or
vertical air inlet and ue outlet via a concentric terminal.
The system is made up from accessories, see diagram 10.30.
NOTE: The air and ue outlets do not have to be equal
lengths. 2x45º bends can replace 1x90º bend if necessary.
The maximum permitted combined (air inlet + ue outlet) ue
length is 20 metres plus terminal assemblies. For each 90°
or
45º
x 2 bends tted, the maximum ue length must be reduced
by 1 metre, see diagram 10.29.
NOTE: When using 90º bends any horizontal run should be
inclined by a minimum of 44mm/metre (2.5º) towards the
boiler to facilitate condense removal.
Alternatively use 45º bends to avoid horizontal runs in the ue
pipe.
Multiple Boiler Chimney Flue Length
The ue length must be calculated and installed according to
the relevant standards EN 13384-1 and 2 (C43 ue systems
only) with reference to the table below and the manufacturers
instructions supplied.
The appliance maximum ue length must be included when
calculating the overall design of the ue system.
Terminal Position
The clearances for a ue outlet are given in the "Flue Location
and Ventilation" section.
In addition the horizontal air inlet must not be closer than 300
mm from a ue outlet on the same wall or 1200mm from an
opposing ue outlet.
Flexicom
12hx
Flexicom
15hx
Flexicom
18hx
Flexicom
24hx
Flexicom
30hx
Flexicom
35hx
Exhaust mass rate (g/s)
At Min Thermal
Load (40C°/30°C)
4.30 4.30 4.30 4.30 4.30 4.30
At Max Thermal
Load (80C°/60°C)
5.54 6.91 8.33 11.17 14.10 16.39
Exhaust temperature (ºC)
At Min Thermal
Load (40C°/30°C)
33.2 33.2 33.2 33.2 33.2 36.0
At Max Thermal
Load (80C°/60°C)
55.8 58.3 63.0 73.3 87.4 84.0
4 METRE EXTENSION
(supplied in packs of 5)
Part No. 0020065480